GB - 21
Safety Function STO
This behaviour can occur either by a short circuit of the IGBTs or by interconnection (also
short circuit) of the control drivers. The error should be regarded as critical, if the drive re
-
mains in STO status.
3.2
Classification of STO according IEC 61508
PFH
2.6 • 10
-12
1/h
PFD
2.3 • 10
-7
on demand
Proof-Test-Interval T
20 years
For SIL classification in connection with the applications consider the failure rates of the ex
-
ternal switch devices for final evaluation.
3.3
Classification of STO according EN ISO 13849
Category
4
MTTF
D
>1000 years
DC
high
For the classification within a performance level in connection with the applications consider
the failure rates of the external switch devices for final evaluation.
3.4
Additional instructions
• The unit must be isolated from mains by main switch when working on parts under volt-
age.
• Mechanical brakes must be installed additionally if external forces have effect to the drive
axis, e.g. vertical axes (hanging loads) or rotary axes with asymmetrical weight distribu
-
tion.
•
For the protection against pollution (pollution degree 2) the installation of the units must
be provided in environment with increased protection (e. g. control cabinet IP 54).
•
Make sure that no small parts fall into the COMBIVERT during assembly and wiring. This
also applies to mechanical components, which can lose small parts during operation.
• Check the safety functions and error responses and generate an acceptance report after
installation.
•
The start-up can be prevented with interruption of the STO signals. STO may not be
released in case of danger according to EN 60204-1. Also note the instructions to the
external safety switch devices.
• Dimension the safety application by way that the corresponding input current of the safety
functions is available for the inputs (see chapter 2.5.1).
Selection of
suitable volt-
age sources
Use for the connection only suitable voltage sources with safe
isolation (SELV / PELV) in accordance with VDE 0100 with nom
-
inal voltage of 24 Vdc ± 10%. Pay attention on a sufficient over
-
voltage category of the voltage supply.