3.3 Unit data
3.3.1 Overview
The technical data are for 2/4-pole standard motors. With other pole numbers the drive
converter must be dimensioned onto the motor rated current. Contact KEB for special or
medium frequency motors.
Unit size
12
13
14
Housing
4
Rated apparent output power
S
out
/ kVA
6.6
8.3
11.4
Max. rated motor power
P
mot
/ kW
4.0
5.5
7.5
Rated output current
I
N
/ A
9.5
12
16.5
Output voltage
U
out
/ V
0…
U
in
or 0…
U
in_dc
/√2
Output phases
3
Output frequency
1)
f
out
/ Hz
0…599
Rated output overload (60 s)
2)
I
60s
/ %
200
150
Rated output overload (3 s)
2)
I
3s
/ %
250
180
Overcurrent
2)
I
OC
/ %
300
216
Rated switching frequency
f
SN
/ kHz
8
4
Rated input current
I
IN
/ A
13
17
21
Rated input voltage
U
N
/ V
400
Input voltage range
U
in
/ V
184…550
Input voltage range DC
U
in_dc
/ V
260…750
Mains phases
3
Mains frequency
f
N
/ Hz
50 / 60
Maximum current 0 Hz / 50 Hz at
f
S
= 8 kHz
I
max_out
/ %
189 / 300
109 / 216
183 / 300
Insulation resistance @
U
_dc
= 500 V
R
iso
/ MΩ
16.67
Table 8:
Overview unit data
1)
The output frequency is to be limited in such a way that it does not exceed 1/10 of the switching
frequency. Units with higher max. output frequency are subject to export restrictions and are only
available on request.
2)
The values refer in % to the rated output current I
N
.
3.3.2 rated operation
All rated values refer to a rated operation at
U
N
= 400 V, rated switching frequency
f
SN
and
an output frequency
f
out
= 50 Hz.
29
UNIT DATA
Summary of Contents for COMBIVERT S6 Series
Page 2: ......
Page 64: ...64 NOTES ...