cONNecTION Of THe POWer UNIT
4.2.3.2 Supply line
The conductor cross-section of the supply line is determined by the following factors:
• Input current of the drive converter
• Used cable type
• Installation method and ambient temperature
• The locally valid electrical regulations
The project engineer is responsible for the design!
4.2.4 Dc connection
4.2.4.1 Connection at DC voltage supply
- -
U
V
W
PE
TA1 TA2
++
+U
-U
Legend
①
DC voltage
260…750 V
②
Fuses
Type aR
Pay attention to the permissible voltage range !
③
KEB COMBIVERT
S6
Figure 14:
Connection at DC voltage supply
4.2.4.2 Terminal strip X1B DC connection
X1b
Name
function
R -- ++ U V W
++
DC connection
- -
Type
Push-In spring connection
Screwdriver blade
08 x 4.5
Stripping length
12 mm
Wire cross-section
AWG 24-8
without wire-end ferrule
0.5...10 mm²
with wire-end ferrule
1.5...6 mm²
Figure 15:
Terminal strip X1B DC connection