brAKe cONTrOL AND TeMPerATUre DeTecTION
4.4.2
Specification and connection of the temperature detection
DANGer
Use only sensors with safe isolation !
Danger to life due to electric shock !
NOTICE
Malfunctions due to incorrect cable or laying!
Malfunctions of the control due to capacitive or inductive coupling.
►
Do not lay cables of the motor temperature sensor (also shielded)
together with the control cable !
►
Cables of the motor temperature sensor inside the motor cable only
permissible with double shielding !
A switchable KTY84/PTC evaluation is implemented in the COMBIVERT. The desired
operating mode can be adjusted by software (dr33).
Operating mode (dr33) resistance
Temperature/state
at too short resistance
short circuit
0 KTY84/130
498 Ω
0°C
1 kΩ
100°C
1,722 kΩ
200°C
1
PTC in accordance
with DIN EN 60947-8
(standard)
0.75…1.5 kΩ (reset resistance)
undefined
1.65…4 kΩ (tripping resistance)
undefined
2 by encoder
digital by the encoder channel
3 KTY83/110
820 Ω
0°C
1670 Ω
100°C
2535 Ω
175°C
4 PT1000
1000 Ω
0°C
1385 Ω
100°C
1758 Ω
200°C
5
free-definable sensor characteristic
at too high resistance
no connection
Table 30:
Specification of the temperature input
4.4.2.1 Operation without temperature detection
Use of the COMBIVERT without evaluation of the temperature input:
• Deactivate the evaluation (pn12 =7).
or
• Install bridge between terminal TA1 (X1C.9) and TA2 (X1C.10) (dr33=1).