Observe coolant flow rate
► Fall below => no sufficient cooling.
►
Exceeding => heat sink is washed out.
Coolant connection
Coolant
Water-glycol (45:55)
Amount of coolant in the device
The amount of coolant is
depending on the system length
Minimum amount of coolant (system length A)
0.125 l
Maximum amount of coolant (system length F)
0.410 l
Coolant inlet temperature
1)
constant, minimum
30°C
constant, maximum
65°C
Minimum volume flow
5 l/min
Maximum volume flow
15 l/min
Rated volume flow
10 l/min
Max. operating pressure in the cooling system
2 bar
Pressure drop
Conditions
Ambient temperature
30°C
Temperature cooling medium
30°C
Cooling medium
Demineralised water
mixed with Longlife
radiator antifreeze C 040
Volume flow in l / min
5
10
15
Pressure drop in bar
System length A
0,037
0,126
0,256
System length B
0,042
0,140
0,284
System length C
0,051
0,171
0,348
System length D
0,054
0,180
0,367
System length E
0,060
0,202
0,412
System length F
0,066
0,221
0,449
Table 18: Technical data coolant
1)
The coolant inlet temperature must always be ≥ than the ambient temperature. A temperature difference
between drive inverter and ambient temperature can lead to condensation at high humidity. Moisture con-
densation is dangerous for the drive inverter. The drive inverter can be destroyed through occuring short-cir
-
cuits. The user must guarantee that any moisture condensation is avoided!