3.3.7 Connection to the coolant for all housing sizes
NOTICE
Damage to the threads
A pairing of G1/4 internal thread and a conical/tapered external thread
is not permitted.
IN
OUT
Name
Version
IN
Coolant inlet G1/4
OUT
Coolant outlet G1/4
Figure 15: Connection to the coolant
It is recommended to connect the G1/4 internal thread together with a G1/4 exter-
nal thread. It is necessary to seal the fitting via the external threading. A suitable
sealing element must be used. Metallic seals should be made of the same material
as the heat sink. The general manufacturer-specific mounting methods apply for
mounting.
55
MECHANICAL DATA