NOTICE
Disturbances via temperature sensor connection
►
Cables for temperature monitoring within the motor cable is only
permissible with double shielding !
4.3.3.1 Connection of a KTY sensor
Sensor
Resistance in kΩ
Temperature in °C
KTY84/130
0,498
0
1
100
1,722
200
Table 23:
Specification of the temperature input
TA1
TA2
+
KTY84
Figure 30:
Connection of a KTY sensor
NOTICE
Störungen durch fehlmessungen
Protection of the motor winding no longer guaranteed.
KTY sensors
are poled semiconductors and
may
• only be operated in the forward direction
(connect the anode to TA1
for this purpose)
.
• not be combined with other observations.
4.3.3.2 Connection of a PT1000 sensor
Sensor
Resistance in Ω
Temperature in °C
PT1000
1000
0
1270,75
70
1385,06
100
Table 24:
Specification of the temperature input
TA1
TA2
PT1000
Figure 31:
Connection of a PT1000 sensor
70
CONNECTION Of THE POWER UNIT