Electrical installation
Operation Manual ServoOne CM-L and ServoOne CM-A
ID no.: 1800.208B.1-00 Date: 03/2020
Electrical installation
4.11 Control connections
ServoOne CM-L charging module
Step
Action
Comment
1.
Make a connection between the connection X3 XC OUT on the
ServoOne CM-L charging module and X3 XC IN on the next device
in the row for the cross-communication.
For this purpose use the cable
supplied of type: XCOM.
See appendix.
2.
As necessary, wire the programmable relay contacts X5 REL
Output: RO02CO/NO and X6 State: RO01NC/CO/NO as well as the
test pulse outputs X6 State: TP00 and TP01.
3.
As necessary, wire X6 State: EXP+ and EXP-.
Connection of the supply unit to
the expansion module on opera-
tion with SO CM BG1+2.
The cable must be twisted
and
shielded if the SO CM axis group
(BG1+2) is housed in a different
cabinet. If the SO CM axis group
is in the same cabinet, the cable
must be twisted but not shielded.
4.
As necessary, wire X6 State: PF, GND.
Power fail. Signals power failure
5.
Wire the thermal contacts X1: BR,
ϑ
Connection for braking resistor
temperature sensor.
6.
Wire the thermal contacts X1:
: ϑ
1
,
ϑ
2
Connection for mains filter (
ϑ
1
)
and mains choke temperature
sensor (
ϑ
2
).
7.
Check all connections again!
X3 XC OUT
X6 State
X5 REL Output
X1:
ϑ
1
, ϑ
2
X1: BR,
ϑ
LEDs: ERR
Voltage
Figure 4.23
Layout, control connections ServoOne CM-L charging module