When a digital input set to "MAN(14)" is activated, the control location P 159[0] -
MPRO_REF_SEL = "TERM" switches (switch to "TERM" is not displayed in the
KeStudio DriveManager 5). In parallel, the reference source is set to the reference
selected via parameter P 164[0] - MPRO_REF_SEL_MAN. The start signal must be
connected to a digital input (ISD0x = Start). The control mode P 300[0] - CON_
CfgCon cannot be switched. The "MAN(14)" mode is displayed in the field bus
control word.
It is
not possible to switch to "MAN" mode
l
when the power stage is active
l
when the drive in the KeStudio DriveManager 5is operated via the manual
mode window.
A level-triggered START P 144[0] - MPRO_DRVCOM_AUTO_START=LEVEL (1) is
ignored in "MAN" mode. After activation of "MAN" mode, the START input must be
reset. When "MAN" mode is ended the motor control also stops.
P No.
Index P Name / Setting
Unit Function
164
0
MPRO_REF_Sel_MAN
Selection of motion profile
OFF (0)
No profile selected
ANA0(1)
Reference value of analogue input ISA0
ANA1(2)
Reference value of analogue input ISA1
TAB(3)
Reference from table
PLC_BASIC(4)
Profile via PLC definition
PLC(5)
Reference from PLC
PARA(6)
Reference via parameter
DS402(7)
Reference via CiA 402 IEC1131
Sercos(8)
Reference via SERCOS
PROFI(9)
Reference via PROFIBUS
VARAN(10)
Reference via VARAN
TWIN(11)
Reference via external option "TWINsync"
HYD(12)
Hydraulic profile (software-specific)
Table 9.6: “Control selector switching” parameters
ID No.: 0842.26B.5-01 Date: 09.2020
ServoOne - Device Help
308
9 Inputs/Outputs settings
P No.
Index P Name / Setting
Unit Function
ANA2(13)
Profile via analogue channel 2 (Technology
option)
ANA2(14)
Profile via analogue channel 3 (Technology
option)
ANA2(15)
Profile via analogue channel 4 (Technology
option)
ANA2(16)
Profile via analogue channel 5 (Technology
option)
TCAM(17)
Table camming (software specific)
Table 9.6: “Control selector switching” parameters (continue)
9.2.7 Power-up sequence
The power-up sequence must be maintained when the drive starts, regardless of the
control mode. If the power-up sequence is followed, the drive starts with a rising
edge of the digital input parameterized to "START" or when the corresponding "Start"
bit is set via a bus system. The reference polarity determines the direction of rotation.
Image 9.4: Time diagram of sequences