Variant 1: Motor calculation
l
Enter the motor data
The motor data relevant to the calculation must be entered from the data
sheet.
l
Click on “Start calculation”.
l
If the moment of inertia of the motor
P 461 - Mot_J
is not known, a value
roughly corresponding to the motor's moment of inertia must be applied.
l
The calculation process can be monitored in the KeStudio DriveManager 5
via the menu, View, Messages.
l
Calculation of operating point: Flux
P 462 - MOT_FluxNom
,
P 340 - CON_
FM_Imag
.
l
Calculation of: current, speed and position control parameters
NOTE
l
All existing motor parameters are overwritten.
Calculated values
l
Flux settings (including for torque constant)
l
Control settings for current controller:
The current controller is dimensioned dependent on the switching frequency
setting.
l
Speed controller and position controller gain:
In this, a moderately rigid mechanism and a 1:1 moment of inertia adjustment
from the load to the motor are to be assumed.
l
V/F characteristic
ID No.: 0842.26B.5-01 Date: 09.2020
ServoOne - Device Help
39
5 Motor
ID
Index Name
Unit
Description
451
0
MOT_Name
Name of motor parameter set
452
0
MOT_CosPhi
Motor rated power factor
455
0
MOT_FNom
Hz
Motor rated frequency
456
0
MOT_VNom
V
Motor rated voltage
457
0
MOT_CNom
A
Motor rated current
458
0
MOT_SNom
rpm
Motor rated speed
459
0
MOT_PNom
kW
Motor rated power
460
0
MOT_TNom
Nm
Motor rated torque
461
0
MOT_J
kg m*m Motor inertia
1530
0
SCD_SetMotorControl
Determination of default control settings
Table 5.5: “Asynchronous motor configuration” parameters
5.4.1 Asynchronous motor electrical data
Image 5.7: “Asynchronous motor electrical data” screen