ID
Value Name
000Dh Data_Free_PEven_EncObs
000Eh Data_PEven
000Fh Data_Free_PEven
001Fh Data_Free
Extra data reading
0020h Data_Free_Free
0021h Data_Free_Free_Free
0022h Data_Free_Free_Free_Free
Table 6.27: SSI mode parameters (all other values are reserved) (continue)
P 636[0] - ENC_CH3_CycleCount = Sampling cycle in: n x 125 µs (microseconds):
ENC_CH3_CycleCount can be used to slow down the timing for the cyclical SSI
encoder evaluation. By default, ENC_CH3_CycleCount = 1, i.e. the default setting
corresponds to 125 µs sampling and cycles for the encoder evaluation. Different
settings must be viewed as special cases and must only be used when necessary.
6.7.8 HIPERFACE DSL® (ServoOne junior)
Ch3: HDSL(7) - HIPERFACE DSL® encoder
NOTE
l
HIPERFACE DSL® is a technology option for the ServoOne junior
that requires special device firmware.
l
For a full description of the HIPERFACE DSL® technology option
(technical data, connections, configuration), see the “Single-cable
interface option 2 Specification” (ID No.: 1106.26B.x).
6.7.9 Encoder gearing
NOTE
l
Please read the general information on encoder gearing found in
Section "Introduction" on page 52 beforehand.
ID No.: 0842.26B.5-01 Date: 09.2020
ServoOne - Device Help
91
6 Encoder
Encoder channels Ch1 to Ch3 each feature their own encoder gearing, while
encoder channel Ch4 (virtual encoders) does not feature
any encoder gearing.
In the case of encoder channel Ch2, it is assumed that the resolver will always be
used as a commutation encoder on the motor shaft. Because of this, the numerator
adjustment range is limited to a value of (+1) or (-1), while the denominator is set at a
fixed value of (+1), for the Ch2 encoder gearing ratio. This means that the only
option available is to invert the encoder signal (direction reversal).
As a whole, the encoder gearing is a scaling factor in the encoder evaluation system
and consists of numerator N (ENC_CHx_Num) for the motor side and denominator D
(ENC_CHx_Denom) for the encoder side (output side).
The following are used to configure the encoder gearing...
l
Ch1 with
P 510[0] - ENC_CH1_Num
and
P 511[0] - ENC_CH1_Denom
,
l
Ch2 with
P 512[0] - ENC_CH2_Num
and
P 513[0] - ENC_CH2_Denom
,
l
Ch3 with
P 514[0] - ENC_CH3_Num
and
P 515[0] - ENC_CH3_Denom
,
parametriert.
P No.
Index Name
Unit Description
510
0
ENC_CH1_Num
Denominator of channel 1
511
0
ENC_CH1_Denom
Numerator of channel 1
512
0
ENC_CH2_Num
Denominator of channel 2
513
0
ENC_CH2_Denom
Numerator of channel 2
514
0
ENC_CH3_Num
Denominator of channel 3
515
0
ENC_CH3_Denom
Numerator of channel 3
Table 6.28: Parameters for encoder gearing