- 5 -
PREPARATIONS
1. FLOOR PLATE AND OUTDOOR AIR CONNEC-
TION
Arrange the floor plate according to the instructions
on page 4 under the heading Floor plate. If you
choose to make your own floor plate, the minimum
dimensions stated in the above-mentioned point must
be followed at all times.
The illustration to the right show the dimensions of
the ready-made floor plate, which is available as an
accessory.
If a connection to the outdoor air is required, a sheet
metal drum must be installed according to one of the
alternatives illustrated, either below or through the
rear wall.
2. FLUE CONNECTION
There are two alternatives for connecting the flue.
Alternative 1: Rear connection
Alternative 2: Top connection
Height from the floor to the centre of the flue at the
rear: 1905
mm
Height from the floor to the height of the connection
top: 2170 mm
Outer diam. of the rear/top sleeve connection: ∅150
For so-called top connection of the chimney, this has
to be done after the stove has been installed. We will
return to this at the end of the Installation instructions
on p. 9.
For so-called rear connection of the stove, this has to
be prepared before the stove is put into place. Note
that side routing and long horizontal routing affect the
draught negatively. For satisfactory function with a
chimney pot of 3.5 m, the length of the horizontal flue
must not exceed 0.5 m.
For more about rear connection, see installation
instruction point 11-14.