F96VTN and G96VTN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
23
See notes at end of table.
(SW1-5 and SW2-2 set to OFF, except as indicated. See Notes 1 and 2.)
Unit Size:
1002122
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches:
SW2-8
SW2-7
SW2-6
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1990
1945
1905
1865
1820
1780
1735
1695
1650
1600
Cooling (SW2-8,7,6)
OFF
OFF
ON
885
800
700
See Note 4
OFF
ON
OFF
1105
1035
955
870
See Note 4
OFF
ON
ON
1255
1190
1125
1055
975
See Note 4
ON
OFF
OFF
1445
1390
1330
1270
1210
1140
1075
See Note 4
ON
OFF
ON
1655
1610
1560
1505
1455
1400
1345
1285
See Note 4
ON
ON
OFF
1990
1945
1905
1865
1820
1780
1735
1695
1650
1600
ON
ON
ON
2135
2095
2060
2025
1985
1945
1905
1865
1820
1780
Maximum Clg Airflow
2
2440
2405
2365
2320
2275
2230
2180
2135
2080
2030
CF Switches
SW2-5
SW2-4
SW2-3
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Low-Clg Default:
OFF
OFF
OFF
885
800
700
See Note 4
Low-Cooling (SW2-5,4,3)
OFF
OFF
ON
740
630
See Note 4
OFF
ON
OFF
885
800
700
See Note 4
OFF
ON
ON
1105
1035
955
870
See Note 4
ON
OFF
OFF
1255
1190
1125
1055
975
See Note 4
ON
OFF
ON
1445
1390
1330
1270
1210
1140
1075
See Note 4
ON
ON
OFF
1655
1610
1560
1505
1455
1400
1345
1285
See Note 4
ON
ON
ON
1990
1945
1905
1865
1820
1780
1735
1695
1650
1600
Cont. Fan Default:
OFF
OFF
OFF
885
800
700
See Note 4
Continuous Fan (SW2-5,4,3)
OFF
OFF
ON
740
630
See Note 4
OFF
ON
OFF
885
800
700
See Note 4
OFF
ON
ON
1105
1035
955
870
See Note 4
ON
OFF
OFF
1255
1190
1125
1055
975
See Note 4
ON
OFF
ON
1445
1390
1330
1270
1210
1140
1075
See Note 4
ON
ON
OFF
1655
1610
1560
1505
1455
1400
1345
1285
See Note 4
ON
ON
ON
1655
1610
1560
1505
1455
1400
1345
1285
See Note 4
Heating (SW1)
High Heat Airflow
3
1810
1765
1720
1675
1625
1575
1525
1475
1425
1375
Low Heat Airflow
3
1405
1350
1290
1225
1160
1100
See Note 4
(SW1-5 and SW2-2 set to OFF, except as indicated. See Notes 1 and 2.)
Unit Size:
1202422
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches:
SW2-8
SW2-7
SW2-6
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
2060
2015
1975
1930
1885
1840
1790
1750
1705
1630
Cooling (SW2-8,7,6)
OFF
OFF
ON
865
775
690
595
505
425
See Note 4
OFF
ON
OFF
1080
1005
935
860
785
705
625
555
490
425
OFF
ON
ON
1285
1220
1150
1085
1020
960
895
820
750
690
ON
OFF
OFF
1465
1410
1350
1285
1230
1175
1115
1060
1000
935
ON
OFF
ON
1685
1635
1585
1530
1475
1420
1375
1325
1270
1225
ON
ON
OFF
2060
2015
1975
1930
1885
1840
1790
1750
1705
1630
ON
ON
ON
2265
2225
2180
2145
2100
2060
2010
1895
1770
1645
Maximum Clg Airflow
2
2320
2310
2270
2230
2190
2135
2020
1895
1770
1645
CF Switches
SW2-5
SW2-4
SW2-3
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Low-Clg Default:
OFF
OFF
OFF
865
775
690
595
505
425
See Note 4
Low-Cooling (SW2-5,4,3)
OFF
OFF
ON
585
470
See Note 4
OFF
ON
OFF
865
775
690
595
505
425
See Note 4
OFF
ON
ON
1080
1005
935
860
785
705
625
555
490
425
ON
OFF
OFF
1285
1220
1150
1085
1020
960
895
820
750
690
ON
OFF
ON
1465
1410
1350
1285
1230
1175
1115
1060
1000
935
ON
ON
OFF
1685
1635
1585
1530
1475
1420
1375
1325
1270
1225
ON
ON
ON
2060
2015
1975
1930
1885
1840
1790
1750
1705
1630
Cont. Fan Default:
OFF
OFF
OFF
865
775
690
595
505
425
See Note 4
Continuous Fan (SW2-5,4,3)
OFF
OFF
ON
585
470
See Note 4
OFF
ON
OFF
730
630
See Note 4
OFF
ON
ON
865
775
690
595
505
425
See Note 4
ON
OFF
OFF
865
775
690
595
505
425
See Note 4
ON
OFF
ON
865
775
690
595
505
425
See Note 4
ON
ON
OFF
865
775
690
595
505
425
See Note 4
ON
ON
ON
865
775
690
595
505
425
See Note 4
Heating (SW1)
High Heat Airflow
3
2165
2120
2075
2030
1985
1940
1895
1850
1770
1645
Low Heat Airflow
3
1675
1625
1575
1525
1475
1425
1375
1325
1275
1225
Table 9 – Cooling
4
and Heating Air Delivery - CFM (Bottom Return
5
with Filter) (Continued)