F96VTN and G96VTN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
A11401
Fig. 32 – Typical Two-Stage Field Wiring Diagram
Table 11 – Electrical Data
A190279
Fig. 33 – Field-Supplied External Electrical Box on Furnace Casing
115-V Wiring
Furnace must have a 115-v power supply properly connected and
grounded.
NOTE:
Proper polarity must be maintained for 115-v wiring. If polarity
is incorrect, control LED status indicator light will flash rapidly (Status
Code 10) and furnace will
NOT
operate.
Verify that the voltage, frequency, and phase correspond to that specified
on unit rating plate. Also, check to be sure that service provided by
utility is sufficient to handle load imposed by this equipment. Refer to
rating plate or
for equipment electrical specifications.
USA Installations
: Make all electrical connections in accordance with
the current edition of the National Electrical Code (NEC) NFPA 70 and
any local codes or ordinances that might apply.
Canada Installations
: Make all electrical connections in accordance
with the current edition of the Canadian Electrical Code CSA C22.1 and
any local codes or ordinances that might apply.
W/W1
W2
COM
Y/Y2
R
G
FURNACE SIZE
VOLTS-
HERTZ-
PHASE
OPERATING VOLTAGE
RANGE
*
*. Permissible limits of the voltage range at which the unit operates satisfactorily.
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY
†
†. Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,
etc.) full load amps.
MINIMUM
WIRE SIZE
AWG
MAXIMUM
WIRE LENGTH
FT (M)
‡
‡. Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
MAXIMUM
FUSE OR
CKT BKR
AMPS
**
**. Time-delay type is recommended.
1
Low Amp Kit (NAHA00101PC) allows select furnaces to be installed with a 15 Amp Breaker and 14 AWG wire within the listed wire length. Affected data shown as Default
Value/Value with Lower Amp Kit.
Maximum*
Minimum*
0401410
115-60-1
127
104
7.0
9.7
14
38
(11.7)
15
0401712
115-60-1
127
104
7.2
9.8
14
37
(11.5)
15
0601412
115-60-1
127
104
7.1
9.7
14
38
(11.7)
15
0601714
115-60-1
127
104
10.9
14.6
14
25
(7.7)
15
0801716
115-60-1
127
104
10.0
13.4
14
27
(8.4)
15
0802120
115-60-1
127
104
14.7/11.2
19.3/14.0
1
12/14
1
29/24
1
(8.8/7.3
1
)
20/15
1
1002120
115-60-1
127
104
14.8/11.3
19.4/15.0
1
12/14
1
29/24
1
(8.8/7.3
1
)
20/15
1
1002122
115-60-1
127
104
12.6
16.7
12
34
(10.5)
20
1202422
115-60-1
127
104
12.6
16.7
12
34
(10.5)
20
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
The cabinet MUST have an uninterrupted or unbroken ground
according to current edition of NEC NFPA 70 or local codes to
minimize personal injury if an electrical fault should occur. In Canada,
refer to the current edition of Canadian Electrical Code CSA C22.1.
This may consist of electrical wire, conduit approved for electrical
ground or a listed, grounded power cord (where permitted by local
code) when installed in accordance with existing electrical codes. Refer
to the power cord manufacturer’s ratings for proper wire gauge. Do not
use gas piping as an electrical ground.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not connect aluminum wire between disconnect switch and furnace.
.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE