background image

K90-KPCS-IM-2

18/04/22

- 13 -

 SYSTEM START-UP CHECK LIST

Only a qualified refrigeration mechanic who is familiar with compressor performance and the function and adjustment of all controls 

and components should start up the compressor. Finishing up work on the installations should be planned so that a qualified mechanic 

IMPORTANT START-UP NOTE

Before any refrigeration system is started, the following items should be checked:

Before any refrigeration system is started, the following items should be checked:

(1)  Check that the wiring diagrams, instructions, bulletins etc. are read and attached to the unit for future reference.

(2)  Check that all electrical and refrigeration connections are tight.

(3)  Check compressor crankcase oil level (if equipped with sight glass). It should be from 1/8 to 1/2 full in the sight glass.

(4)  Ensure that compressor shipping spacers (spring mounted compressors) or hold down nut (solid mounted compressors are 

properly in place.

(5)  Check that the compressor discharge and suction shut-off valves are open.

(6)  Ensure that the high and low pressure controls (see table below), pressure regulating valves, oil pressure safety controls and 

any other safety controls are adjusted properly.

(7)  Check all motors, fans and pump bearings in the condenser and evaporator. If they are the types that require oil or grease, 

make sure that this is attended to in accordance with the tag, which will be attached. Fan blades and pumps should be checked 

for correct rotation, tightness and alignment. Air should be drawn through the condenser (air cooled condensing unit models).

(8)  Electric and hot gas evaporator fan motors should be temporarily wired for continuous operation until the room temperature 

has stabilized.

(9)  Observe the system pressures during the charging and initial operation process. 

DO NOT

 add oil while the system is low on 

refrigerant charge unless the oil level is dangerously low.

(10)  Continue to charge the system until it has enough charge for proper operation. 

DO NOT OVERCHARGE THE SYSTEM.

 Note that 

bubbles in the sight glass may not necessarily mean a shortage of refrigerant. It could be caused by a restriction.

After the system is started, pay attention to the following:

(1) 

DO NOT

 leave the system unattended until the system has reached its normal operating condition and the oil charge has 

properly adjusted itself to maintain the proper level in the sight glass. 

(2)  Compressor performance, and that of all of the moving components, should be watched carefully throughout the first operating 

cycle and then checked periodically during the first day of operation. 

 

Three phase scroll compressors must be checked for correct rotation. During the initial start up, observe the suction and discharge 

gauges to ensure the suction pressure drops and the discharge pressure rises.

WARNING

Extreme care must be used when starting compressors for the first time after the system has been charged. During this time liquid 

refrigerant may have migrated to the compressor crankcase, creating a condition that could cause the compressor damage due to 

slugging. Energizing a crankcase heater (if so equipped) 24 hours prior to start-up is recommended. If the compressor is not equipped 

with a crankcase heater, directing a 500 watt heat lamp or other safe heat source on the lower shell or crankcase of the compressor 

for approximately thirty minutes is recommended unless machine room is at above 65°F for at least 24 hrs prior to startup.

CAUTION

Summary of Contents for Parallel

Page 1: ...ogram Service Parts Availability Equipment Start Up Information Product Support Resources As Built Service Parts List Parallel Compressor Systems Installation and Maintenance Manual Air Water and Remo...

Page 2: ...to those ordered and to electrical power avail able at the job site Save all shipping papers tags and instruction sheets for reference by installer and owner NOTE Accessories such as drier cores run...

Page 3: ...essary rigging should be engaged to set the Rack into position Lifting lugs have been provided along the base frame c channels for attaching lifting slings Spreader bars and lifting slings should be s...

Page 4: ...ATIONAL REFRIGERATION AND AIR CONDITIONING PRODUCTS INC THIRD ANGLE PROJECTION 2 ALL DIM S ARE OUTSIDE DIM S UNLESS SPECIFIED 1 FOR STANDARD TOLERANCES REFER TO DOCUMENT EN 311 3 HEADER BODY ENDS ARE...

Page 5: ...pply through a properly sized branch circuit protection disconnect switch The entering service fuse must not exceed the maximum overcurrent protection MOP value on the unit data plate Field connected...

Page 6: ...this is approximately 1 3 psig 9 0 kPa for R 404A At the temperatures encountered in the condenser receiver and liquid line a certain amount of oil is always being circulated with the refrigerant thr...

Page 7: ...cities at reduced refrigerant flow IMPORTANT PIPING NOTE REFRIGERANT PIPING cont d IMPORTANT All suction lines outside of the refrigerated space must be insulated During the lower capacity running mod...

Page 8: ...ed on each condenser or at compressors to control fan cycling and split circuiting Refrigeration controller may require field program ming to perform major functions as per available data All the set...

Page 9: ...ruments Copper jumper lines should be used to interconnect both high and low pressure sides of the system These lines should be at least 3 8 O D in order to handle the light density vapor at high vacu...

Page 10: ...ng a low temperature system Blend type refrigerants 400 series i e R404A must not be vapor charged unless the cylinder is completely emptied into the system Weigh the refrigerant drum before and after...

Page 11: ...em R 12 R 22 R 502 Copeland Ultra 22CC A A P Mobil EAL ARTIC 22 CC A A P ICI Virginia KMP Emkarate RL 32CF A A P Thermal Zone 22CC A A P Witco Suniso 3GS P P PM Texaco Capella WF32 P P PM Calumet RO15...

Page 12: ...is more than doubled as compared with conventional lubricants Special care should be taken Refer to Bitzer Technical Bulletin KT 510 2 section 5 for additional information COMPRESSOR OILS cont d Refri...

Page 13: ...e temporarily wired for continuous operation until the room temperature has stabilized 9 Observe the system pressures during the charging and initial operation process DO NOT add oil while the system...

Page 14: ...l down can cause structural problems in pre fabricated rooms and will damage crack concrete floors Reduce room temperature by 10 to 15 F 5 6 to 8 4 C per day Hold this temperature for 24 to 48 hours a...

Page 15: ...and will result in piston ring wear piston and cylinder wall damage If adjustment to the suction superheat is required it should be done either by adjusting the thermostatic expansion valve at the eva...

Page 16: ...than the compressor nameplate values 6 To check the high pressure control setting it is necessary to build up the head pressure to the cut out point of the control This can be done by stopping the con...

Page 17: ...lay 6 Motor windings damaged 7 Internal compressor mechanical damage Compressor starts but trips on overload protector 1 Improperly wired 2 Low line voltage 3 Loose wiring 4 Defective start or run cap...

Page 18: ...b charge Suction pressure too low 1 Shortage of refrigerant 2 Evaporator dirty or iced up 3 Clogged liquid line filter drier 4 Clogged suction line filter or compressor suction strainers 5 Expansion v...

Page 19: ...thermostat improper setting defective time clock 2 Electric heaters defective miswired low voltage 3 Not enough defrosts per day 4 Air defrost evaporator operating at too low of temperature require e...

Page 20: ...locked off to avoid accidental start up of the equipment 1 Check electrical components and tighten any loose connections 2 Check all wiring and electrical insulators 3 Check contactors to ensure prop...

Page 21: ...K90 KPCS IM 2 18 04 22 21 NOTES...

Page 22: ...porator terminals L1 L2___________ L2 L3 ____________ L1 L3__________ Amperage at evaporator L1___________ L2____________ L3______________ Expansion valve Manufacturer____________________________ Mode...

Page 23: ...email parts k rp com call 1 844 893 3222 x525 email orders k rp com call 1 844 893 3222 x501 email shipping k rp com call 1 844 893 3222 x503 web k rp com warranty email warranty k rp com call 1 844 8...

Page 24: ...s product improvement we reserve the right to make changes without notice KeepRite Refrigeration Brantford ON Longview TX 1 800 463 9517 info k rp com www k rp com AS BUILT SERVICE PARTS LIST Service...

Reviews: