background image

K90-KPCS-IM-2

18/04/22

- 16 -

When the system has been running trouble free for an extended time (two weeks or more) and design conditions are satisfied, the 

following check list should be followed:

(1)  Check that compressor 

discharge and suction pressures

 are operating within the allowable design limits for the 

 

compressor. If not, take the necessary corrective action.

(2)  Check the liquid line sight glass and expansion valve operation. If there is an indication that the system is low on 

 

refrigerant, thoroughly 

check the system for leaks before adding refrigerant.

(3)  Check the 

level of the oil

 in the compressor sight glass (if so equipped). Add oil as necessary.

(4)  The thermostatic expansion valve must be checked for 

proper superheat settings

. The sensing bulb must have 

 

positive contact with the suction line and should be insulated. Valves operating at a high superheat setting results 

 

in low refrigeration capacity. Low superheat settings can cause liquid slugging and compressor bearing washout. 

 

(Refer to the section on compressor and evaporator superheats)

(5)  Check the 

voltage and amperage

 readings at the compressor terminals. Voltage reading must be within the 

 

recommended guidelines. Normal operating amperages can be much lower than the compressor nameplate 

 values.

(6)  To check the 

high pressure control setting

 it is necessary to build up the head pressure to the cut-out point of 

 

the control. This can be done by stopping the condenser fan(s) (air cooled condensing units) or pump and 

 

watching the pressure rise on a high pressure gauge to make sure the high pressure control is operating at the 

 setting.

(7)  Check the 

low pressure settings

 by throttling the compressor shut-off valve and allowing the compressor to    

 

 

 pump 

down. This operation must be done with extreme caution to avoid too sudden a reduction in crankcase   

 

 

 

pressure, which will cause oil slugging and possible damage to the compressor valves. Close the valve a turn a  

 

 

 

a time while watching the compound gauge for change and allowing time for the crankcase pressure to equalize  

 

 

 

with the pressure control bellows pressure. The slower the pressure is reduced, the more accurate will be the   

 

 

 

check on the pressure control setting. 

(8)  Recheck all 

safety and operating controls

 for proper operation and adjust as necessary.

(9) Check 

defrost controls for initiation and termination settings

, and the length of defrost period. Set the fail    

 

 

 

safe on the time clock at the length of defrost plus 25 %. 

(10)  If the system is equipped with winter head pressure controls (fan cycling or flooded valves), 

check for operation

.

(11)  Fill in the 

Service Log

 in the back of this Installation Manual. 

SYSTEM OPERATIONAL CHECK LIST

Summary of Contents for Parallel

Page 1: ...ogram Service Parts Availability Equipment Start Up Information Product Support Resources As Built Service Parts List Parallel Compressor Systems Installation and Maintenance Manual Air Water and Remo...

Page 2: ...to those ordered and to electrical power avail able at the job site Save all shipping papers tags and instruction sheets for reference by installer and owner NOTE Accessories such as drier cores run...

Page 3: ...essary rigging should be engaged to set the Rack into position Lifting lugs have been provided along the base frame c channels for attaching lifting slings Spreader bars and lifting slings should be s...

Page 4: ...ATIONAL REFRIGERATION AND AIR CONDITIONING PRODUCTS INC THIRD ANGLE PROJECTION 2 ALL DIM S ARE OUTSIDE DIM S UNLESS SPECIFIED 1 FOR STANDARD TOLERANCES REFER TO DOCUMENT EN 311 3 HEADER BODY ENDS ARE...

Page 5: ...pply through a properly sized branch circuit protection disconnect switch The entering service fuse must not exceed the maximum overcurrent protection MOP value on the unit data plate Field connected...

Page 6: ...this is approximately 1 3 psig 9 0 kPa for R 404A At the temperatures encountered in the condenser receiver and liquid line a certain amount of oil is always being circulated with the refrigerant thr...

Page 7: ...cities at reduced refrigerant flow IMPORTANT PIPING NOTE REFRIGERANT PIPING cont d IMPORTANT All suction lines outside of the refrigerated space must be insulated During the lower capacity running mod...

Page 8: ...ed on each condenser or at compressors to control fan cycling and split circuiting Refrigeration controller may require field program ming to perform major functions as per available data All the set...

Page 9: ...ruments Copper jumper lines should be used to interconnect both high and low pressure sides of the system These lines should be at least 3 8 O D in order to handle the light density vapor at high vacu...

Page 10: ...ng a low temperature system Blend type refrigerants 400 series i e R404A must not be vapor charged unless the cylinder is completely emptied into the system Weigh the refrigerant drum before and after...

Page 11: ...em R 12 R 22 R 502 Copeland Ultra 22CC A A P Mobil EAL ARTIC 22 CC A A P ICI Virginia KMP Emkarate RL 32CF A A P Thermal Zone 22CC A A P Witco Suniso 3GS P P PM Texaco Capella WF32 P P PM Calumet RO15...

Page 12: ...is more than doubled as compared with conventional lubricants Special care should be taken Refer to Bitzer Technical Bulletin KT 510 2 section 5 for additional information COMPRESSOR OILS cont d Refri...

Page 13: ...e temporarily wired for continuous operation until the room temperature has stabilized 9 Observe the system pressures during the charging and initial operation process DO NOT add oil while the system...

Page 14: ...l down can cause structural problems in pre fabricated rooms and will damage crack concrete floors Reduce room temperature by 10 to 15 F 5 6 to 8 4 C per day Hold this temperature for 24 to 48 hours a...

Page 15: ...and will result in piston ring wear piston and cylinder wall damage If adjustment to the suction superheat is required it should be done either by adjusting the thermostatic expansion valve at the eva...

Page 16: ...than the compressor nameplate values 6 To check the high pressure control setting it is necessary to build up the head pressure to the cut out point of the control This can be done by stopping the con...

Page 17: ...lay 6 Motor windings damaged 7 Internal compressor mechanical damage Compressor starts but trips on overload protector 1 Improperly wired 2 Low line voltage 3 Loose wiring 4 Defective start or run cap...

Page 18: ...b charge Suction pressure too low 1 Shortage of refrigerant 2 Evaporator dirty or iced up 3 Clogged liquid line filter drier 4 Clogged suction line filter or compressor suction strainers 5 Expansion v...

Page 19: ...thermostat improper setting defective time clock 2 Electric heaters defective miswired low voltage 3 Not enough defrosts per day 4 Air defrost evaporator operating at too low of temperature require e...

Page 20: ...locked off to avoid accidental start up of the equipment 1 Check electrical components and tighten any loose connections 2 Check all wiring and electrical insulators 3 Check contactors to ensure prop...

Page 21: ...K90 KPCS IM 2 18 04 22 21 NOTES...

Page 22: ...porator terminals L1 L2___________ L2 L3 ____________ L1 L3__________ Amperage at evaporator L1___________ L2____________ L3______________ Expansion valve Manufacturer____________________________ Mode...

Page 23: ...email parts k rp com call 1 844 893 3222 x525 email orders k rp com call 1 844 893 3222 x501 email shipping k rp com call 1 844 893 3222 x503 web k rp com warranty email warranty k rp com call 1 844 8...

Page 24: ...s product improvement we reserve the right to make changes without notice KeepRite Refrigeration Brantford ON Longview TX 1 800 463 9517 info k rp com www k rp com AS BUILT SERVICE PARTS LIST Service...

Reviews: