background image

INSTALLATION INSTRUCTIONS

R−410A, Two−Stage Split System Air Conditioner

421 01 6002 01

11

COMPRESSOR OPERATION

The basic scroll design has been modified with the
addition of an internal unloading mechanism that opens
a by−pass port in the first compression pocket, effectively
reducing the displacement of the scroll.  The opening and
closing of the by−pass port is controlled by an internal
electrically operated solenoid.  The modulated scroll uses
a single step of unloading to go from full capacity to
approximately 67% capacity.

A single speed, high efficiency motor continues to run
while the scroll modulates between the two capacity
steps.  Modulation is achieved by venting a portion of the
gas in the first suction pocket back to the low side of the
compressor, thereby reducing the effective displacement
of the compressor.

Full capacity is achieved by blocking these vents, thus
increasing the displacement to 100%.  A DC solenoid in
the compressor, controlled by a rectified external 24 volt
AC signal, moves the slider ring that covers and uncovers
these vents.

The vent covers are arranged in such a manner that the
compressor operates at approximately 67% capacity
when the solenoid is not energized and 100% capacity
when the solenoid is energized.  The loading and
unloading of the two step scroll is done “on the fly” without
shutting off the motor between steps.

NOTE: 67% compressor capacity translates to
approximately 80% cooling or heating capacity at the
indoor coil.

The compressor will always start unloaded and stay
unloaded for five seconds even when the second stage
of the thermostat is calling for more capacity (a starting
advantage under low voltage conditions).

TROUBLESHOOTING

Models are factory equipped with the Comfort Alert

UltraTech

 Diagnostics device (refer to Figure 12) in the

control box.  Comfort Alert UltraTech

 

provides

compressor staging from low to high and high to low
capacity.  Comfort Alert UltraTech provides
around−the−clock monitoring for common electrical
problems, compressor defects, and broad system faults.
If trouble is detected, an alert code is displayed with a
flashing LED indicator. Alert codes are listed in Figure 13.

The device is factory wired and requires no
modification. 
Low voltage lead wires are provided in the
control box for connection to thermostat wires (use wire
nuts).

The Comfort Alert UltraTech must be powered to properly
stage compressor to high capacity.  Energizing the Y (Y1)
terminal operates the compressor in low−stage.  Both the
Y (Y1) and Y2 terminals must be energized for
high−stage operation.

The Comfort Alert UltraTech device operates by
monitoring the compressor power leads and the
thermostat demand signals Y (Y1) and Y2 terminals.  It
draws constant 24 VAC power at the R and C terminals.

When the compressor is operating in low−stage (Y or Y1),
the 24v DC compressor solenoid coil is de−energized.
When the compressor is operating in high−stage (Y or Y1
and Y2), the 24v DC solenoid coil is energized.  The 24v
DC plug that is connected to the compressor does NOT
have an internal rectifier.  DO NOT INSTALL A PLUG
WITH INTERNAL RECTIFIER.

Figure 12 Comfort Alert

t

 UltraTech

t

 Diagnostics

Y2

Y

L

R
C

R

C

S

“Power” LED

Thermostat Demand
1

st

 Stage Compressor

Data Port

Thermostat Signal

24 VAC HOT

24 VAC Common

DC Compressor
Solenoid

“Alert” LED

“Trip” LED

Thermostat Demand
2

nd

 Stage Compressor

Summary of Contents for R?410A

Page 1: ...ner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels W...

Page 2: ...or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit...

Page 3: ...les Wall 6 152mm 24 610mm Service Wall Wall Wall 6 152mm 6 152mm Post Wall Wall 18 457mm 18 457mm 18 457mm 18 152mm 6 152mm 6 152mm 6 152mm 18 457mm 18 457mm 18 457mm 18 457mm 24 610mm Service 24 610m...

Page 4: ...ture is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roof a release must be obtained from the building owner to free the...

Page 5: ...le avoiding unnecessary bends and turns Always insulate the entire suction line Both lines should be insulated when routed through an attic or when routed through an underground raceway When routing r...

Page 6: ...are plugged from the factory Outdoor units are shipped with a refrigerant charge sealed in the unit Leave the service valves closed until all other refrigerant system work is complete or the charge w...

Page 7: ...system is free of air and water Watch the vacuum gauge as the system is pulling down The response of the gauge is an indicator of the condition of the system refer to Figure 7 With no leaks in the sy...

Page 8: ...mum to 253 volts maximum 60 Hz single phase Outdoor units are approved for use with copper conductors only Do not use aluminum wire Refer to unit rating plate for minimum circuit ampacity and circuit...

Page 9: ...r example a 25 foot 7 6m line set is 10 feet 3m longer than the specified 15 feet 4 6m Add 0 6 ounces 17g charge for each of the extra 10 feet 3m 10 x 0 6 6 0 ounces additional charge 3m x 17g 51g add...

Page 10: ...42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 SEQUEN...

Page 11: ...d stage of the thermostat is calling for more capacity a starting advantage under low voltage conditions TROUBLESHOOTING Models are factory equipped with the Comfort Alert UltraTech Diagnostics device...

Page 12: ...for Y2 to be energized test the voltage output at the plug with a DC voltmeter The reading here should be 4 to 18 volts If NOT unplug the harness from the module and check voltage at the DC Sol pins o...

Page 13: ...age 4 Faulty metering device Check TXV bulb installation size location and contact Check if TXV is stuck closed or defective 5 Condenser coil is dirty 6 Liquid line restriction filter drier blocked 7...

Page 14: ...pply and the compressor S terminal 3 Compressor start winding is damaged Check compressor motor winding resistance Yellow ALERT Flash Code 7 Open Run Circuit Current only in start circuit 1 Open circu...

Page 15: ...HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Reviews: