R−410A, Two−Stage Split System Air Conditioner

14

421 01 6002 01

Status LED

Status LED Description

Status LED Troubleshooting  Information

Yellow “ALERT”
Flash Code 5

Open High Voltage Circuit 1. Outdoor unit power disconnect is open

2. Compressor circuit breaker or fuse(s) is open

3. Compressor contactor has failed open

 Check compressor contactor wiring and connections

 Check for compressor contactor failure (burned, pitted, open)

 

Check wiring and connectors between supply and compressor

 Check for low pilot voltage at compressor contactor coil

4. Open circuit in compressor supply wiring or connections

5. Unusually long compressor protector reset time due to

extreme ambient temperature

6. Compressor windings are damaged

 Check compressor motor winding resistance

Yellow “ALERT”
Flash Code 6

Open Start Circuit
Current only in run circuit

1. Run capacitor has failed

2. Open circuit in compressor start wiring or connections

 Check wiring and connectors between supply and the

compressor “S” terminal

3. Compressor start winding is damaged

 Check compressor motor winding resistance

Yellow “ALERT”
Flash Code 7

Open Run Circuit
Current only in start circuit

1. Open circuit in compressor run wiring or connections

 Check wiring and connectors between supply and the

compressor “R” terminal

2. Compressor run winding is damaged

 Check compressor motor winding resistance

Yellow “ALERT”
Flash Code 8

Welded Contactor
Compressor always runs
continuous operation

1. Compressor contactor has failed closed

2. Thermostat demand signal not connected to module

Yellow “ALERT”
Flash Code 9

Low Voltage
Control circuit < 17

 

VAC

1. Control circuit transformer is overloaded

2. Low line voltage (contact utility if voltage at disconnect is low)

 Check wiring connections

 Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated.

 TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.

 Reset ALERT Flash code by removing 24VAC power from module (R terminal).

 Last stored ALERT Flash code is displayed for one minute after module is powered on.  The code must flash a 

total of one minute before it will clear.

Summary of Contents for R?410A

Page 1: ...ner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels W...

Page 2: ...or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit...

Page 3: ...les Wall 6 152mm 24 610mm Service Wall Wall Wall 6 152mm 6 152mm Post Wall Wall 18 457mm 18 457mm 18 457mm 18 152mm 6 152mm 6 152mm 6 152mm 18 457mm 18 457mm 18 457mm 18 457mm 24 610mm Service 24 610m...

Page 4: ...ture is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roof a release must be obtained from the building owner to free the...

Page 5: ...le avoiding unnecessary bends and turns Always insulate the entire suction line Both lines should be insulated when routed through an attic or when routed through an underground raceway When routing r...

Page 6: ...are plugged from the factory Outdoor units are shipped with a refrigerant charge sealed in the unit Leave the service valves closed until all other refrigerant system work is complete or the charge w...

Page 7: ...system is free of air and water Watch the vacuum gauge as the system is pulling down The response of the gauge is an indicator of the condition of the system refer to Figure 7 With no leaks in the sy...

Page 8: ...mum to 253 volts maximum 60 Hz single phase Outdoor units are approved for use with copper conductors only Do not use aluminum wire Refer to unit rating plate for minimum circuit ampacity and circuit...

Page 9: ...r example a 25 foot 7 6m line set is 10 feet 3m longer than the specified 15 feet 4 6m Add 0 6 ounces 17g charge for each of the extra 10 feet 3m 10 x 0 6 6 0 ounces additional charge 3m x 17g 51g add...

Page 10: ...42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 SEQUEN...

Page 11: ...d stage of the thermostat is calling for more capacity a starting advantage under low voltage conditions TROUBLESHOOTING Models are factory equipped with the Comfort Alert UltraTech Diagnostics device...

Page 12: ...for Y2 to be energized test the voltage output at the plug with a DC voltmeter The reading here should be 4 to 18 volts If NOT unplug the harness from the module and check voltage at the DC Sol pins o...

Page 13: ...age 4 Faulty metering device Check TXV bulb installation size location and contact Check if TXV is stuck closed or defective 5 Condenser coil is dirty 6 Liquid line restriction filter drier blocked 7...

Page 14: ...pply and the compressor S terminal 3 Compressor start winding is damaged Check compressor motor winding resistance Yellow ALERT Flash Code 7 Open Run Circuit Current only in start circuit 1 Open circu...

Page 15: ...HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Reviews: