R−410A QUICK REFERENCE GUIDE
•
R−410A refrigerant operates at 50% − 70% higher pressures than R−22. Be sure that servicing equipment and
replacement components are designed to operate with R−410A.
•
R−410A refrigerant cylinders are rose colored.
•
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
•
R−410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
•
Manifold sets should be 750 psig high−side and 200 psig low−side with 520 psig low−side retard.
•
Use hoses with 750 psig service pressure rating.
•
Leak detectors should be designed to detect HFC refrigerant.
•
R−410A, as with other HFC refrigerants, is only compatible with POE oils.
•
Vacuum pumps will not remove moisture from oil.
•
Do not use liquid line filter−driers with rated working pressures less than 600 psig.
•
Do not install a suction line filter−drier in liquid line.
•
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
•
POE oils may cause damage to certain plastics and roofing materials.
•
Wrap all filter−driers and service valves with wet cloth when brazing.
•
A liquid line filter−drier is required on every unit.
•
Do not use with an R−22 TXV.
•
If indoor unit is equipped with an R−22 TXV, it must be changed to an R−410A TXV.
•
Never open system to atmosphere while it is under a vacuum.
•
When system must be opened for service, break vacuum with dry nitrogen and replace all filter−driers.
•
Do not vent R−410A into the atmosphere.
•
Do not use capillary tube indoor coils.
•
Observe all WARNINGS, CAUTIONS, NOTES, and bold text.