3 Installation
Power Conversion System BCS-B-H Series (1000K-1500K)
User Manual
36
All rights reserved © Kehua Data Co., Ltd.
Figure3-18
Wiring diagram of DC side
When connecting the input wires of DC side, the input current of BCS1000K-B-H should not exceed
1603A, the input current of BCS1250K-B-H should not exceed 1754A, the input current of
BCS1500K-B-H should not exceed 1871A. We suggest using bolt M16 to fasten DC wires,
corresponding torque is 750~1000 Kgf.cm.
To ensure safety running of the PCS, when wiring, the fasten bolt must be led from back of the terminal
bar, as shown in Figure3-19.
Figure3-19
Bolt installation direction diagram
Step 6
After finishing the wiring and ensure all connection is right and ensure there is no overlap joint, no
stress among the wires and plates, then, seal the empty part with fireproofing mud.
Step 7
Install the wiring cover plate again.
----End