4 Touch Screen Operation
Power Conversion System BCS-B-H Series (1000K-1500K)
User Manual
60
All rights reserved © Kehua Data Co., Ltd.
Figure4-43
Password set page
After login, user can modify the password.
Energy calibration
In the
Setting
page, click
Energy Calibration
icon, the touch screen will enter the corresponding
page, as shown in Figure4-44.
Figure4-44
Energy calibration page
When the total charge and total discharge value is not in accordance with the external meter, user can
correct
the
total
charge
and
total
discharge
value,
the
correction
value
of
total
charge/discharge=measured charge/discharge value on meter - showed total charge/discharge value.
Detailed setting as follows.
Step 1
Enter "energy correction" page according to the operation above.
Step 2
Click the box at the right of the total charge/discharge, it will pop up a small keyboard, enter the
calculated correction value and then click "ENTER" to confirm the operation.