7 Troubleshooting
Power Conversion System BCS-B-H Series (1000K-1500K)
User Manual
70
All rights reserved © Kehua Data Co., Ltd.
7 Troubleshooting
This chapter mainly introduces the dispose methods of general faults.
7.1 Rectifying Common Faults
Once the PCS fault, the ALARM indicator lights on, the buzzer sends alarm, and the touch screen
shows the current fault, at the same time, the PCS halts. The typical faults and solutions are as shown
When PCS faults, it is strictly prohibited to restart the PCS via touch screen. It can be restarted only
make sure that the PCS is OK after disconnecting the power, or, it may damage the PCS.
Table7-1
Troubleshooting
Phenomenon
Possible reason
Solution
Battery
over-voltage
Battery voltage exceeds the
max. allowable battery voltage
1.
Check if the battery configuration is
proper and the voltage within the input
voltage range.
2.
Contact the battery manufacturer in time.
Battery
under-voltage
Battery voltage exceeds the min.
allowable battery voltage.
1.
Check if the battery configuration is
proper and the voltage within the input
voltage range.
2.
Contact the battery manufacturer in time.
Battery
under-voltage
with heavy load
The power larger than the
setting apparent power for a
certain ratio and the battery
1.
Check if the battery configuration is
proper and the voltage within the input
voltage range.