Power Conversion System BCS-B-H Series (1000K-1500K)
User Manual
A Technical Specifications
All rights reserved © Kehua Data Co., Ltd.
81
Model
Item
BCS1000K-B-H
(440Vac)
BCS1250K-B-H
(550Vac)
BCS1500K-B-H
(600Vac)
Rated grid frequency (Hz)
50/60
Grid frequency range
(Hz)
49.5
~
50.2 (settable)\59.5~60.2 (settable)
Power factor
>0.99(rated power)
0.8 ahead
~
0.8 lag (adjustable)
Grid-tied current THDi
<3%(rated power)
Off-grid mode
Rated output power (kW)
1000
1250
1500
Max. output power
(kVA)
1100
1375
1650(10min)
Rated output voltage
440,3
φ
550,3
φ
660,3
φ
THDu
<3%(linear load)
Rated frequency(Hz)
50/60
Overload
capacity
of
resistive load
For 110% rated load, long-time
running;
For 120% rated load, protect after
1min.
For 110% rated
load,
protect
after 10min;
For 120% rated
load,
protect
after 1min.
Insulation way
Without built-in transformer
Mechanical part
Size (W×H×D)(mm)
Without girder: 1400
×
2000
×
800
With girder: 1400
×
2063
×
800
Weight (kg)
1370
Environment and
safety
Protection grade
IP20
Cooling mode
Forced wind-cooling (smart fan speed adjusting)
Altitude (m)
0~4000 (>2000 derating)
Relative humidity
0~95% (with no condensation)