Hybrid Inverter
User Manual
3 Installation
43
CT direction is: inverter
→
grid, please connected properly!
Smart meter setting
Step 1 If the smart meter is connected, please do the following setting.
If the meter used in the grid side of iStoragE1 product, address is set to A-001.
If the meter used in the PV inverter grid side, address is set to A-002.
When there is a PV inverter in the user's home, it is recommended to install the smart meter in
the grid output side of the PV inverter to ensure the accuracy of grid electricity statistics, and the
address is set to A-002. As shown in the Figure3-51 and Figure3-53.
When using the zero-export function, the following setting are required:
1.
Set the "Zero-export function" to enable in " Basic setting".
Figure3-54 Set "Zero-export function"
Zero-export function