Hybrid Inverter
User Manual
4 APP Operation
59
Set Generation/Export limit control – Hard limit control.
In the "
Other setting
" item, you can enable Generation/Export limit control– Hard limit control.
Figure4-17 Hard limit control
Set "
Volt-watt response mode
".
In the "
Grid setting
" item, select "Linear" in "
P-V mode
" to enable Volt-watt response mode,
Volt-watt response mode is for charging of multiple mode inverter with energy storage.
When connecting the multiple mode inverter, the two internal N wires should be connected and the N
wire should not be connected to grounding in the grid-tied and off-grid states. The connection diagram
is shown below.
Figure4-18 N wire connection diagram
Set "
Volt-var response mode
".
In the "
Grid related setting
" item, select "
On
" in "
Q-V mode
" to enable "
Volt-var response mode
".