KR-RM Series(1
~
3kVA) UPS
User Manual
4
Installation
All rights reserved ©Xiamen Kehua Hengsheng Co., Ltd.
21
No.
Check items
3
Check the grounding wire: whether the grounding wire of UPS connects with the
grounding terminal bar of the machine room reliably.
4
Check whether the voltage between the neutral wire and the grounding wire is less than
5Vac.
5
If the user configuration is the long delay model, check whether the battery wire between
UPS and the battery cabinet connects correctly and reliably.
6
If UPS installs the remote monitoring device, check whether the related RS232 port
connects correctly.
7
Check whether the wiring is neat and the wire binding is in accordance with the process
specification.
8
Check whether the installation and wiring are good for system reformation, expansion and
maintenance in future.