MR33 Series (75K-600K) Modular UPS
User Manual
5 Use and Operation
All rights reserved ©Kehua Hengsheng Co., Ltd.
91
5.3.3 UPS Shutdown
If the system bypass normal, after the UPS shutdown, system will turn to bypass power supply mode;
if system bypass abnormal, after the UPS shutdown, system will be with no output. Before shutting
down, please ensure that the load is closed.
Step 1
Shut down the user load.
Step 2
Shut down the inverter.
Shut down the inverter by panel OFF combination button 1
Long press the panel OFF combination button for 3s, system will turn to bypass supply power
from inverter output. Check the system running status on the touch screen, and ensure that the
system has turned to bypass output from inverter to supply power.
Shut down the inverter by touch screen 2
In main page, click
icon, it will enter ON/OFF page, as shown in Figure5-3, click
OK
button to perform the shutdown operation..
Figure5-3
ON/OFF page
Step 3
Disconnect the external battery switch
→
POWER switch
→
BYPASS switch
→
OUTPUT
switch.