MR33 Series (75K-600K) Modular UPS
User Manual
A Technical Specifications
All rights reserved ©Kehua Hengsheng Co., Ltd.
105
A
Technical Specifications
Model
Index
MR33
75
MR33
125
MR33
200
MR33
300
MR33
400
MR33
500
MR33
600
Input
Input mode
3
φ
4W+PE
Rated input voltage
(VAC)
220/230/240 (phase voltage)
Input voltage range
Vin=176Vac~280Vac, it does not need to decrease rated power to use
Vin=80Vac~175Vac, for linear load, it is necessary to decrease rated
power to use
Input frequency range
(Hz)
40~70
Bypass
synchro
tracking range (Hz)
50/60±6
Bypass input voltage
(VAC)
220/230/240 (phase voltage)
Input power factor
≥
0.99
Input THDi
Resistive full load:
≤
3%; non-linear full load:
≤
5%
Battery voltage (VDC)
+180~+276
(
can be selected in the range of +15 pieces to +23 pieces, for
MR3375, MR33125 and MR33200, the default is +16 pieces, for other
models, the default is +20 pieces
)
Charge current (A)
Power module amount *10 (max)