MR33 Series (75K-600K) Modular UPS
User Manual
2 Overview
All rights reserved ©Kehua Hengsheng Co., Ltd.
19
NO.
Name
Illustration
○
4
Ready switch
Place the ready switch to “unlock” status, the indication
color is green, the bypass module is not locked with the
cabinet, and at this time, the bypass module can be
dismantled.
Place the ready switch to “lock” status, the indication color
is red, the bypass module is locked with the cabinet, and at
this time, the bypass module cannot be dismantled.
○
5
Battery start button
At the status of no mains, bypass, press the button for 2s, the
system will start from battery status.
2.5.6 System Control Box
The system control box unit is as shown inFigure2-12.
Figure2-12
System control box unit
Table2-4
Illustration for system control box unit
NO.
Name
Illustration
○
1
Reserved slot position of
expansion card
Install corresponding function expansion card according to
function requirements
○
2
SNMP card (optional)
It can realize the remote manage for the UPS. Detail operation
and setting please see the user manual of network adapter.
○
3
System control card
Manage the module output, and control the system parallel
operation and output double busbar synchronization. The
lower is system card 1, The upper is system card 2.
○
4
System monitor card
Includes communication port, output dry contact and input dry
contact.