MR33 Series (75K-600K) Modular UPS
User Manual
3 Installation
All rights reserved ©Kehua Hengsheng Co., Ltd.
37
The wiring groove requirements of MR series UPS is the same, in above figure, we take MR33400 as
an example to illustrate.
The recommended wiring groove size is as follows: for MR3375, MR33125, MR33200, MR33300
:
A
×
D
×
H
:
650
×
200
×
300(mm)
;
for MR33400, MR33500, MR33600
:
A
×
D
×
H: 245
×
500
×
300(mm).
Step 1
Determine and plan the installation position according to the UPS size (as shown in Figure3-8,
Figure3-9) and installation clearance requirement (see3.2.3 Installation Space).
Figure3-8
Size of MR3375, MR33125, MR33200, MR33300
Figure3-9
Size of MR33400, MR33500, MR33600