3 Installation
MY-A Series (10kVA-20kVA) UPS
User Manual
38
This series UPS's battery input adapt positive and negative battery group (battery group has 8~10
positive cell and corresponding negative cell, which 12V/cell, default has 10 positive cell and
corresponding negative cell).
Figure3-19 shown the 10kVA wiring method: one battery cabinet has 20 cells and one 3P breaker, the
external wiring includes BATT.+, BATT.- and BATT. N.
Figure3-20 and Figure3-21 are shown the 15kVA/20kVA wiring methods.
Wiring methods one: there are 20 cells separately connect to two external battery port, every
battery cabinet has one 3P breaker, the external wiring includes BATT.+, BATT.- and BATT. N,
as shown in Figure3-20.
Wiring methods two: there are 20 cells connect to each external battery port, every battery
cabinet has one 3P breaker, the external wiring includes BATT.+, BATT.- and BATT. N, as shown
See Table3-2 for selection of breaker capacity.