3Installation
String PV Grid-tied Inverter SPI-B-H Series (175K-250K)
User Manual
20
All rights reserved ©Kehua Hengsheng Co.,
Ltd.
Figure3-6
Back-to-back installation space requirements (unit: mm)
3.3.3 Installation method
It is recommended to install the inverter vertically or obliquely backwards (with an angle of
≤
15
°
from the vertical plane). It cannot be tilted forward, inverted installed.
Figure3-7
Illustration of installation method
Because the air duct of the inverter is designed for the downward air inlet and the upper air outlet, in
order to ensure the normal operation of the inverter, it is not recommended to install it horizontally.
3.3.4 Installation carrier requirements
The installation carrier of the inverter (such as walls and brackets) should meet the requirements
shown in Figure3-8.