3Installation
String PV Grid-tied Inverter SPI-B-H Series (175K-250K)
User Manual
34
All rights reserved ©Kehua Hengsheng Co.,
Ltd.
Two external ground terminals are reserved at the bottom of the inverter, at least one of them should be
selected for grounding.
In order to improve the anti-corrosion performance of the ground terminal, it is recommended to apply
anti-rust paint on the outside of the ground terminal for protection after the bottom line is installed.
The grounding of the inverter and the lightning rod of the inverter installation building cannot be
the same, the two need to be separated (as shown inFigure3-28).
The ground of the inverter should be directly connected to the grounding system, and the
impedance is less than 20mΩ.
Figure3-28
The grounding of inverter
----End
3.6.4 AC output wiring
Before connecting to the power grid, first make sure that the power grid voltage and frequency meet
the requirements of the inverter. For detailed parameters, see
. Otherwise, please
contact the power company to resolve.