background image

the  dilution  tee  may  be  used  to  ensure  that  the  oxygen  content  of  the  exhaust  is  high  enough  to 
maintain  the  burner  flame  during  the  smoke  cycle.  the  dilution  tee  also  enables  the  velocity  in  the 
cyclone to be maintained at a suitable value to ensure efficient separation of any fluidising medium, while 
the velocity in the fluidised bath exhaust duct may be limited to reduce the amount of fluidising medium 
entrained.

a correctly adjusted system should result in a minimal loss of fluidising medium from the fluidised bath. 
the majority of the entrained medium should be retained by the cyclone, from where it may be returned 
to the bath. the fume concentration within the ducting should be below the LeL (lower explosion limit) 
for  the  various  products  generated  during  the  cleaning  process.  the  exhaust  emission  from  the 
afterburner outlet should be within locally acceptable limits. the environment adjacent to the fluidised 
bath should have gas concentrations within locally accepted tLV (threshold limit values).

setting the extrAction system

1. 

Switch on the extraction system setting the dampers initially as follows:

 

  

dilution tee 50%

 

  

damper 50%

2. 

heat up the bath to the working temperature, adjusting the air flow for correct fluidisation.

3. 

When at the working temperature, adjusting the damper so that any fine dust particles omitted 
from the surface of the bath are just entrained by the extraction system.

4. 

operate as above for 30 minutes.

5. 

Switch off the extraction system and check:

 

a.  the amount of sand in the collector bin (cyclone)

 

b.  the amount of sand in the duct

6. 

If there is more than 2" of sand in the bin ensure that fluidisation is not excessive and that the bath 
was not overfilled. tip the sand back into the bath.

7. 

If 6 is satisfactory check that the extraction rate is not excessive.

 

note:  if A lid is used on the BAth, ensure thAt it is not Airtight

8. 

If there is sand in the afterburner the velocity through the cyclone is incorrect. therefore open the 
dilution tee and increase damper so that system still just entrains fines. re-check the system from 4.

9. 

check the operation of the afterburner. Set the flame to maximum (gate valve fully open).

10.  With the afterburner running immerse 

slightly

 contaminated component.

11.  check fume extraction above the bath visibly ensuring all fumes are extracted 
 

ie: drager to check concentration. check the Lower explosive Limit.

12.  check the visible smoke from the stack, check the fume concentration is acceptable.

13.  If the visible smoke is present or the fume concentration is too high decrease the smoke generation 

rate, ie: reduce the temperature of the bath.

14.  When 11 is satisfactory, immerse a maximum contamination item and re-check as 11.

15.  repeat  14  and  decrease  the  flame  size  until  conditions  are  just  acceptable  to  minimise  gas 

consumption.

8

Summary of Contents for Bibby Scientific Techne Afterburners AB-100

Page 1: ...AB 100 AB 500 Afterburners operator s manual Issue 3 5 08 ...

Page 2: ...tion 1 Specification 3 Operator Safety 4 Guarantee 4 Contact Information 5 INSTALLATION 6 Commissioning 7 Setting the Extraction System 8 OPERATION 9 Maintenance 9 Fault Finding 9 ILLUSTRATION of AB 100 10 Wiring diagram 11 ...

Page 3: ...s both the ignition system and the pilot solenoid valves are energised Once the flame probe has detected that the pilot flame is correctly established the ignition system is switched off and the burner operates on the pilot flame only for a period of approximately 15 seconds after which the main solenoid valves are energised to establish the main flame If the pilot flame is not established correct...

Page 4: ...ust ductwork after the cyclone s and filter and scrubber if used but before the Afterburner In addition the exhaust ductwork should contain a damper valve to enable the rate of fume removal to be adjusted according to system requirements A dilution tee should be positioned between the fluidised bath and the cyclone s to be optimised and to ensure that the oxygen content of the exhaust fumes is suf...

Page 5: ...3 5kPa 10 14 inch WG Propane 2 5kPa to 3 5kPa 10 14 inch WG AB 500 Overall external dimensions approx Height 2500mm Width 1200mm Depth 1000mm Outlet spigot 305mm Burner rating 6kW to 120kW 20 000 BTU hr to 400 000 BTU hr Fuel consumption range Natural gas 0 6m3 hr to 12m3 hr 20 to 400 ft3 hr Butane 0 2m3 hr to 4m3 hr 6 to 120 ft3 hr Propane 0 26m3 hr to 5 2m3 hr 9 to 180 ft3 hr Gas supply pressure...

Page 6: ...closed guarantee card This period is from the date of purchase and within this period all defective parts will be replaced free of charge provided that the defect is not the result of misuse accident or negligence Servicing under this guarantee should be obtained from the supplier Notwithstanding the description and specification s of the units contained in the Operator s Manual and Service Manual...

Page 7: ...nsole positioning a lockable manual shut off valve close to the Afterburner to ensure safety during maintenance periods etc Connect a single phase electrical supply to the input terminals in the control cabinet see rating plate for details The base of the control cabinet may be machined to accept suitable conduit The electrical supply to the Afterburner should be interlocked with the motor starter...

Page 8: ...ted above the main gas flow manual adjusting valve and adjust the internal screw A pilot flame of sufficient size to successfully sustain the flame control system in the ON position is needed Once the pilot flame has been successfully established and detected by the flame probe the main gas solenoid valves will be heard to open as they are energised The main gas flow limiter or ballofix valve adja...

Page 9: ...at any fine dust particles omitted from the surface of the bath are just entrained by the extraction system 4 Operate as above for 30 minutes 5 Switch off the extraction system and check a The amount of sand in the collector bin cyclone b The amount of sand in the duct 6 If there is more than 2 of sand in the bin ensure that fluidisation is not excessive and that the bath was not overfilled Tip th...

Page 10: ...outine The period between checks depends upon the types of materials being treated in the fluidised bath and the frequency at which the system is used a Check ignition electrode clean and replace as necessary b Check the condition of the burner plates and clean if necessary Note excessive deposits of fluidising medium on the burner plate are an indication of poor system adjustment or incorrect mai...

Page 11: ...x control valve Pressure gauge Gate valve Insulation Pilot solenoid valve Additional gas pressure regulator required for propane Manual gas shut off valve supplied by customer Pilot gas pressure regulator Main gas pressure regulator Main gas safety shut off valves Exhaust Ø200 Air flow detector Inlet Ø100 Gas supply 3 4 gas fitting AB 100 ...

Page 12: ...11 ...

Page 13: ...ng the details below UK Office Keison Products P O Box 2124 Chelmsford Essex CM1 3UP England Tel 44 0 330 088 0560 Fax 44 0 1245 808399 Email sales keison co uk Please note Product designs and specifications are subject to change without notice The user is responsible for determining the suitability of this product ...

Reviews: