background image

 

Operators

 

 use the product for its intended function. They must be trained in electrical safety procedures and proper use of

the instrument. They must be protected from electric shock and contact with hazardous live circuits.

 

Maintenance personnel

 

 perform routine procedures on the product to keep it operating, for example, setting the line volt-

age or replacing consumable materials. Maintenance procedures are described in the manual. The procedures explicitly
state if the operator may perform them. Otherwise, they should be performed only by service personnel.

 

Service personnel

 

 are trained to work on live circuits, and perform safe installations and repairs of products. Only properly

trained service personnel may perform installation and service procedures.

The 

 symbol on an instrument indicates that the user should refer to the operating instructions located in the manual.

The 

symbol on an instrument shows that it can source or measure 1000 volts or more, including the combined effect

of normal and common mode voltages. Use standard safety precautions to avoid personal contact with these voltages.

The 

 

WARNING

 

 heading in a manual explains dangers that might result in personal injury or death. Always read the as-

sociated information very carefully before performing the indicated procedure.

The 

 

CAUTION

 

 heading in a manual explains hazards that could damage the instrument. Such damage may invalidate the

warranty.

 

Operation

 

Exercise extreme caution when a shock hazard is present. Lethal voltage may be present on cable connector jacks or test
fixtures. The American National Standards Institute (ANSI) states that a shock hazard exists when voltage levels greater
than 30V RMS, 42.4V peak, or 60VDC are present. 

 

A good safety practice is to expect that hazardous voltage is

present in any unknown circuit before measuring.

 

For maximum safety, do not touch the product, test cables, or any other instruments while power is applied to the circuit
under test. ALWAYS remove power from the entire test system and discharge any capacitors before: connecting or discon-
necting cables or jumpers, installing or removing switching cards, or making internal changes, such as installing or remov-
ing jumpers.

Do not touch any object that could provide a current path to the common side of the circuit under test or power line (earth)
ground. Always make measurements with dry hands while standing on a dry, insulated surface capable of withstanding the
voltage being measured.

Do not exceed the maximum signal levels of the instruments and accessories, as defined in the specifications and operating
information, and as shown on the instrument or test fixture panels, or switching card.

Chassis connections must only be used as shield connections for measuring circuits, NOT as safety earth ground connections.

If you are using a test fixture, keep the lid closed while power is applied to the device under test. Safe operation requires
the use of a lid interlock.

 

Maintenance and Service

 

Inspect the connecting cables, test leads, and jumpers for possible wear, cracks, or breaks before each use. Before perform-
ing any maintenance, disconnect the line cord and all test cables.

 

Cleaning

 

Keep the connections free of contaminants (such a dirt, oil, etc) in order to maintain maximum insulation resistance. If the
connections become contaminated, clean them thoroughly with methanol and allow them to dry completely before use.

!

 

2

Reviews: