Model 4200A-SCS Parameter Analyzer Reference Manual
Section 13: LPT library function reference
4200A-901-01 Rev. C / February 2017
13-97
Pulsers
4225-PMU
Pulse mode
Standard and Segment Arb
Details
Errors caused by the connections and cable length between the 4225-PMU and the device under test
(DUT) can be corrected by using connection compensation. When connection compensation is
enabled, each DUT measurement factors in either the default or measured (custom) compensation
values.
Use this command to control connection compensation. You can select short or delay. Short
compensation corrects for the measured resistance of the cabling and connections. Delay
compensation measures and corrects for cable delay (the time it takes a signal to transit the cable).
You can use either default connection compensation values (PMU or RPM) or custom connection
compensation values. The default values provide compensation for simple connection setups that use
the supplied cables. The custom connection compensated values are generated when connection
compensation is performed. The custom values provide optimum compensation.
Custom connection compensation is a two-part process:
1. Perform connection compensation from the Clarius interface (see
(on page 5-32)). Connection compensation data is generated for short and delay
conditions. The compensation values are stored in tables.
2. Use this command (
pulse_conncomp
) to enable the custom connection compensation values.
When a test is run, each measurement factors in the enabled compensation values. If connection
compensation is disabled, the compensation values are not used by the test.
Example
pulse_conncomp(PMU1, 1, 1, 3);
This example assumes connection compensation was done using the Clarius interface. This command
enables short connection compensation using the custom compensation values.
Also see
None