Model DMM7510 7½ Digit Graphical Sampling Multimeter Reference Manual
Section 3: Functions and features
DMM7510-901-01 Rev. B / May 2015
3-81
Config list next block
The config list next block recalls the settings at the next index of a configuration list.
When trigger model execution reaches a configuration recall next block, the settings at the next index
in the specified configuration list are restored.
The first time the trigger model encounters this block for a specific configuration list, the first index is
recalled. Each subsequent time this block is encountered, the settings at the next index in the
configuration list are recalled and take effect before the next step executes. When the last index in
the list is reached, it returns to the first index.
The configuration list must be defined before you can use this block.
When you select the Config List block, the following option is available.
Setting
Description
Config List
The name of the configuration list from which to recall the next
index.
Config list prev block
The config list prev block defines a trigger model block that recalls the settings stored at the previous
index in a configuration list.
The configuration list previous index trigger block type recalls the previous index in a configuration
list. It configures the settings of the instrument based on the settings at that index. The trigger model
executes the settings at that index before the next block is executed.
The first time the trigger model encounters this block, the last index in the configuration list is recalled.
Each subsequent time trigger model execution reaches a configuration list previous block for this
configuration list, it goes backward one index. When the first index in the list is reached, it goes to the
last index in the configuration list.
You must create the configuration list before you can define it in this building block.
When you select the config list prev block, the following option is available.
Setting
Description
Config List
The name of the configuration list from which to recall the previous
index.
Config list recall block
The configuration list recall block loads a specific index from a configuration list.
All parameters that are defined in the configuration index are changed and take effect before this
block completes and the next block begins.
In most cases, you should load the first configuration index at the beginning of the trigger model to
ensure that the correct initial state is set and that the trigger model is repeatable.
You must define the configuration list before you can define it in this block.
When you select the config list recall block, the following options are available.
Setting
Description
Config List
The name of the configuration block to recall the index from
Recall Index
The index to recall