15
VOLTAGE LIMITS ON TERMINALS A & N
Maximum Supply Voltage
260VAC
Minimum Supply Voltage
190VAC
SUPPLY VOLTAGE LIMITATIONS
VOLTAGE LIMITS ON TERMINALS LV & N
Maximum Supply Voltage
25VAC 50Hz or 25VDC
Minimum Supply Voltage
18VAC 50Hz or 18VDC
RELAYS
The E30 houses 2 relays. Both relays are SPST with normally open
contacts. Relay 1 is normally regarded
as the pump control relay and
relay 2 is normally regarded as the alarm relay. When operating the E30
as a dual pump controller, relay 2 is used to control the second pump.
With the HD terminal linked to the NO terminal of Relay 1, the E30
can directly control a single phase motor up to 2.4kW. Without the
HD terminal link in place, relays 1 & 2 are limited to directly
controlling a motor to 0.75kW. Both relays can control motors of
any size via interposing contactors.
CONTACT RATINGS FOR RELAYS 1 & 2
16A at 250VAC
Resistive Load PF > 0.9
16A at 30VDC
Resistive Load PF > 0.9
50mA at 5VDC
Minimum Load