35
to 290 psi in increments of 1 kPa or 1 psi depending on the pressure units
you have chosen to use. The high-pressure trip point will ordinarily be set
to some value that is well above the low-pressure trip point. If you attempt
to set the high-pressure trip point to a pressure that is lower than the low-
pressure trip point, you will invoke a pressure warning from the E30 to
check your pressure settings. If the system pressure rises to above the
high-pressure trip point the E30 will immediately shut down the system and
close its alarm relay contacts and display a message to the effect that the
pressure is too high.
If you choose not to use the high-pressure trip point and leave it set to 0 the
E30 reverts to providing low-pressure protection only for the system. When
set up this way the E30 will start the system using its start-up timer and will
expect to see the system pressure rise to above whatever low-pressure
trip point you have set, before the start-up timer times out. Once above the
low-pressure trip point the E30 will run the system without any regard to a
high-pressure limit. If the pressure falls to below your low-pressure trip
point the E30 will run its run-on timer and if pressure fails to rise above the
low-pressure trip point by the end of the run-on, the E30 will shut the system
down and display a message that the system pressure is too low.
When operated in the mode described above the E30 does not provide any
high-pressure trip point. However, the E30 has an operating pressure
range that is limited to 2000 kPa or 290 psi. If the system pressure exceeds
this limit for any reason and reaches 2200 kPa or 430 psi the E30 will
automatically shut down the system and display a message that its 22 Bar
excess pressure limit has been exceeded. The 22 Bar, 2200 kPa, 430 psi
limit is not adjustable and is intended to protect the E30’s built in pressure
sensor against excess pressure.
SPECIAL FUNCTIONS
Mode 3
In mode 3 you can choose to use either relay 1 or relay 2 as your preferred
output device. Relay 1 is the primary relay and it is intended to drive heavy
loads. Relay 1 can be used on its own as a set of voltage free contacts or
it can be used in conjunction with the HD solid state drive to directly control
pump motors up to 2.4kW single phase or of any required size via an
interposing contactor. The timers built into relay 1 limit the speed the relay
can open and close to about 1.5 seconds per cycle. This is perfectly
Summary of Contents for E30
Page 11: ...11 74mm 60mm 4 X 6mm Holes TOP WALL BRACKET DRILL PATTERN...
Page 19: ...19 WIRING DIAGRAMS PLUG PLAY CONNECTIONS CONNECTIONS FOR A SINGLE PHASE PUMP...
Page 20: ...20 LOW VOLTAGE AC SUPPLY WITH REMOTE INPUT CONNECT AN EXTERNAL ALARM...
Page 21: ...21 TWO SINGLE PHASE PUMPS WITH A REMOTE INPUT LOW VOLTAGE DC SUPPLY REMOTE INPUT...