background image

Specification and Operating Instructions

KLT11-D Temperature Digital Controller

Description

Installation

NOTE: Unit must be mounted away from vibration, impacts, 
water and corrosive gases.

Cut hole in panel 

2.80 x 1.14 inches)

 Apply silicone (or rubber gasket) around the perimeter of 

the hole to prevent leakage.

 Insert unit into hole of panel.
 Slide removable fitting clips onto unit from the back until 

secure to panel.

 Wiring diagram is displayed on the top of the unit

NOTE: DO NOT INSTALL PROBE CABLE NEAR POWER 
CABLES.

The KLT11 is designed for many heating and cooling 
applications. It has an input for temperature probe type PTC 
or NTC 

The probe temperature is 

displayed on the bright 3-digit display. The user is able to 
program 16 different parameters including set point, 
hysteresis, cycle time and ambient probe adjustment using 
the silicone front keypad. The KLKey input allows an easy 
programming of the parameters. The unit features error   
warning and password protection. Select between red, 
green or blue display color, temperature display in ºC or ºF 
and 115Vac, 230Vac,   24Vac/dc or 12Vac/dc power supplies.

The model reference is given by: KLT11 - DWXYZ
Where each sufix can take the following values:

=

=

X

Display Color

R=Red, G=Green, B=Blue

Y

Supply Voltage

110=115Vac, 230=230Vac
24=24Vac/dc, 12=12Vac/dc

Z

Units

C=ºC, F=ºF

• 


(selectable by parameter).

Model references

W

Output

Null  16A(1HP), 2  20A(2HP)

71 x 29 mm (

Technical Data

Supply voltages

115Vac±10%, 230Vac±10%, 24Vac/dc±10%, 12Vac/dc±10%

Supply powers

4VA (230V/115V) 1,5VA(24V /12V) 

1% of full scale

0,1º (3 digits)

Display

3-digit and sign (red, green or blue)

Output 

1HP Model

SPDT Relay Resistive load 16A
1HP 240Vac -- 10FLA, 60LRA 240Vac

2HP Model

SPST Relay Resistive load 20A
2HP 240Vac -- 12FLA, 72LRA 240Vac

Dimensions

Front 77 x 36 mm  Depth  62 mm (3.03 x 1.42 x 2.44 inch)

Front Protection  

IP64

Storage temperature

-20ºC to 80ºC (

-

4 to 176ºF)

Operating temperature

0ºC to 70ºC (32 to 158ºF)

Probe range

PTC -50ºC to 150ºC (-58 to 302ºF)
NTC -50ºC to 110ºC (-58 to 230ºF)

Accuracy

Better than 

Resolution

Probe Input 

(Selectable by parameter)

PTC1000 probes (25ºC - 1000 Ohm) / NTC

KLKey Input

For an quick programming of  all parameters

Wiring Diagram

1  2

7  8  9 10 11

SUPPLY

POWER

Probe input

OUTPUT

NC  COM   NO

1  2

7  8  9 10

S U PP LY

P OW ER

P ro be input

OUTPUT

NO  CO M    

1HP Mode

l

2HP Mode

l

E L E C T R O N I C A

E L E C T R O N I C A

ETDT1700I_110207

  Electrónica Keld, S.L.                                                                                 Phone: +34 976 429 099 
 Pol.Ind. Empresarium. C/Lentisco, 15

    Fax:+34 976 593 532 

 50720 - La Cartuja Baja, ZARAGOZA

 E-mail: keld@keld.es 

 Spain

Web: http://www.keld.es  

Reviews: