KCO-NO2  User’s  Manual 

90-0201-01 

Kele • 3300 Brother Blvd. • Memphis, TN  38133

  

Page: 6

 

WWW.KELE.COM 

3  Electrical Installation 

The controller is not equipped with a power switch; it is operational whenever sufficient power is 
applied to the low voltage power input terminals (do not connect to line).   
All electrical connections to the controller are made through screw terminals that can be unplugged 
during wiring.  The controller’s enclosure contains multiple conduit knockouts for flexibility during 
installation; refer to Figure

 2

 and Figure

 1

 for details and dimensions of the enclosures. 

3.1  Analog Reporting-Output Connections 

Each sensor’s readings are individually reported by the 
controller’s two powered 4-20mA analog output 
connections.  Current flows out of the ‘+’ terminal and 
returns to the ‘-‘terminal. 
The CO output is provided at the terminals highlighted 
green in Figure 3 and the NO

2

 output is provided at the 

terminals highlighted yellow in Figure 3.  The analog 
output connection has polarity as labeled on the controller 
silkscreen: care must be taken to ensure proper 
connection.  To wire the analog output connections: 

1.

 

Power down the controller,.  This can be done by 
unplugging the controller power terminal  
(See Figure 6

).

 

2.

 

Unplug the desired analog output screw terminal (either the NO

2

 or CO terminal). 

3.

 

Connect the signal wires paying close attention to the polarity.  

4.

 

Plug the analog output screw terminal back into the controller. 

5.

 

Repeat this process for both analog outputs, then reconnect power.  

3.2  Relay Connections 

The controller has two SPDT dry-contact relay output terminals (shown in Figure 4).  The relays are 
UL rated at 10 Amps at up 277 VAC, and the associated circuitry meets UL criteria for connection 
to line voltage below 300 volts.  Some jurisdictions may require such heavy gauge wires that the 
full capabilities of the relays are not operationally 
achievable. 
The relay connections have three-terminal screw 
connectors that allow devices to be wired to the 
controller in either normally-open (

NO

) or normally-

closed (

NC

) configuration.  These outputs are activated 

when ambient air concentrations rise above the 
controller threshold settings (refer to 

Section 4.3

 for 

more information). 
In the 

NO Configuration

, the voltage attached to the 

NO

 

terminal will be present at the 

COM

 terminal only when 

the relay output is activated. 
In the 

NC Configuration

, the voltage attached to the 

NC

 

terminal will be present at the 

COM

 terminal while the 

relay output is deactivated: the voltage attached to the 
NC terminal is removed when the relay output is activated. 

Figure 4: Relay Outputs 
 

 

FIGURE 3

: Location of Analog Output 

Terminals

.

 

Summary of Contents for KCO-NO2

Page 1: ...PRELIMINARY KCO NO2 Sensor User s Manual 90 0201 01 ...

Page 2: ... Manual 90 0201 01 Kele 3300 Brother Blvd Memphis TN 38133 Page 2 WWW KELE COM Revision History Revision Date Changes 90 0201 00 3 18 21 Original Issue 90 0201 01 4 12 21 Change CO sensor ToS to 200 ppm from 100 ppm ...

Page 3: ...n 7 4 Operational Description 8 4 1 Normal operation 8 4 2 Startup 9 4 3 Setting Warning and Alarm Threshold 10 4 4 Warning and Alarm Conditions 10 4 5 Abnormal operation 10 5 Sensor Calibration 11 5 1 Calibration Gases 11 5 2 Calibration Procedure 13 6 Sensor Module Replacement 14 6 1 Sensor Errors 14 6 2 Replacement Sensors 14 6 3 Field Replacement of Sensor Modules 14 7 Warranty 15 7 1 Duration...

Page 4: ...W Control Relays Two separate SPDT relays for warning and alarm outputs UL rated 10 Amps max at 277 VAC RMS or 30 VDC Concentration Reporting Outputs Two powered 4 20 mA current loop outputs one for each sensor 4 mA output 0 ppm 20 mA full scale output Maximum loop resistance 510Ω Termination Pluggable screw terminals for use with 12 AWG or thinner wire Stranded wire recommend for 18 AWG or heavie...

Page 5: ...ibration free surface near the middle of the area to be monitored about 5 feet above the floor It should be located where there is free airflow avoid corners or recesses The air vents on the sides of the enclosure should not be closer than 1 foot from the nearest perpendicular wall and must not be obstructed or painted over May be mounted in any orientation but hinge on the left side is most commo...

Page 6: ...igure 6 2 Unplug the desired analog output screw terminal either the NO2 or CO terminal 3 Connect the signal wires paying close attention to the polarity 4 Plug the analog output screw terminal back into the controller 5 Repeat this process for both analog outputs then reconnect power 3 2 Relay Connections The controller has two SPDT dry contact relay output terminals shown in Figure 4 The relays ...

Page 7: ...ed to the controller s relay output to the COM location of screw terminal 5 Plug the relay output screw terminal back into the correct location on controller board 3 3 Power Connection Power connection to the controller is made at the two terminal screw connector located at the bottom right side of the board highlighted in Figure 6 Power to the controller can be either AC or DC voltage DC voltage ...

Page 8: ...unciator when elevated levels of carbon monoxide generated by gasoline engines and abbreviated CO or nitrogen dioxide from diesel engine exhaust and abbreviated NO2 are detected If the concentration of either gas exceeds its programmed alarm value a second set of alarm contacts is operated to trigger an alarm The controller has two independent sensor modules one for sensing carbon monoxide CO the ...

Page 9: ...reshold the WARNING relay is deactivated the same action occurs for the ALARM relay The front cover has two LEDs indicators one for the CO and the other for the NO2 sensor module These LEDs illuminate different colors to indicate normal green warning yellow alarm red and error blinking red conditions see Table 3 The concentrations of CO and NO2 in the ambient air are reported at each senor s analo...

Page 10: ...s change color to indicate the controller s current operational status Table 3 shows the behavior of the front panel LEDs during normal operation Two dry contact SPDT relays are provided on the controller these relays activate during warning and alarm conditions Refer to Section 3 3 for location and wiring information Readings for the two sensors are independently reported on the controller s two ...

Page 11: ...or instructions on how to assemble and operate its gas supply components Each sensor must be sequentially calibrated with two different gases The Zero gas is the same for both sensors and is used for the zero calibration which must be done first The span gas is different for each sensor and used for the span calibration which MUST be done ONLY AFTER a successful zero calibration Each calibration i...

Page 12: ...KCO NO2 User s Manual 90 0201 01 Kele 3300 Brother Blvd Memphis TN 38133 Page 12 WWW KELE COM FIGURE 10 Calibration Flowchart This procedure must be done twice first as Zero then as Span for each sensor ...

Page 13: ...f not If successful blinking GREEN The sampling completed successfully Disconnect the gas and press the same button that started the calibration again for 3 seconds indicating the cal gas has been removed The LED then blinks GREEN YELLOW for 2 minutes indicating that the calibration was accepted If NOT successful blinking RED The sampling can be re started while the LED is blinking RED by pressing...

Page 14: ...or has failed When front panel status LED is blinking red the sensor is no longer operational and must be replaced 6 2 Replacement Sensors Calibrated sensor modules are available from Kele Carbon Monoxide CO Nitrogen Dioxide NO2 Cal Kit KMOD CO KMOD NO2 UCK 3 kit 6 3 Field Replacement of Sensor Modules Sensor modules must be replaced when they reach their End of Life To replace a sensor module 1 O...

Page 15: ...r ensuring that any product into which Products are incorporated other components used with DCS Products and the purposes for which DCS Products are used are appropriate and compatible with those Products If Kele determines that a returned Product does not conform to this warranty it will at Kele s discretion either repair or replace that Product and will ship the Product back to Buyer free of cha...

Page 16: ...he sensor has reached the end of its operating life and must be replaced Contact Kele for a calibrated replacement module In harsh environments a sensor may fail prematurely During normal operation the sensor is regularly tested to detect common failures If a failure is detected the front panel status LED for that sensor will blink red and its concentration reporting analog output will stay at 20 ...

Reviews: