©2014 4Front Engineered Solutions, Inc.
14
6004752K — aFX-C Dock Leveler — Safe
T
Frame
®
March 2014
probLeM
possibLe CaUse
soLUTion
1) Leveler will not fit properly in pit.
a) Pit is out of square with the sides.
b) One side and rear angle is out of
square.
c) Pit floor irregular in rear.
d) Pit is too deep.
a1) Align the sides parallel and equally
spaced with the rear frame angle
touching the rear curb angle in one
place. Fill the gap between the rear
curb angle and rear frame angle using
shims in weld noted in Fig. 10. See
Fig 20.
b) Align the leveler with the two square
edges. The gap on the sides should
be even in the most narrow section
(1/2" Max. per side). See Fig. 21.
c) If large deformations exist in the
concrete work, attempt to flatten
out the rough surface using a chisel
or grinder to take out the large
obstructions. The rear leveling legs
can be installed on out of plane
surfaces up to 1/8" at each leg. See
Fig. 22.
d) Weld 4" x 4" shims to the bottom of
the adjustable legs as shown in Fig 4.
insTaLLaTion,
continued
insTaLLaTion TroUbLesHooTing
The following procedures apply after the leveler is level in
the pit.
Shim and weld flush
Equal
gap
1/2" max.
Fig. 21
1/8" MAX
Allowable Step
No Greater than
1" x 3" in size
6"
Contact
Zone
Fig. 22
Fig. 20