BOTTLE COOLER

OPERATION

CAUTION:  DO NOT THROW ITEMS INTO THE STORAGE AREA. FAILURE TO HEED THESE 

RECOMMENDATIONS COULD RESULT IN DAMAGE TO THE INTERIOR OF THE 

CABINET.

REFRIGERATED CYCLE

During the refrigeration cycle, the evaporator fans wilt run continuously even when 
one or more doors are open. The door switch will activate the lights when opened.
1.   Every 6 hours, the unit will turn off and to allow the evaporator coil to defrost. The 

controller now displays the defrost symbol. When the coil temperature reaches 
41°F or after 20 minutes of defrost, the unit will turn on again.

2.  Anti-condensation heaters on door frames work in conjunction with the 

compressor.

3.   The factory setting for the temperature range is 34°F to 38° F.

CONTROL PANEL SOLID-STATE THERMOSTAT 

FRONT PANEL COMMANDS
SET

 

SET: To display target set point; in programming mode it selects a 
parameter or confirms an operation.

 

DEF: To start a manual defrost

 

UP: To view the last alarm occurrence; in programming mode it browses 
the parameter codes or increases the display value

 

DOWN: To view the last alarm occurrence; in programming mode it 
browses the parameter codes or decreases the display value

Key Combination:

  To lock & unlock the keyboard

  To enter in programming mode
  To return to the room temperature display

LED

MODE

FUNCTION

On

Compressor enabled

Flashing Programming phase (flashing with  )

Anti-short cycle delay enabled

On

Defrost enabled

Flashing Programming phase (flashing with  )

Dripping in progress

Service and Installation Manual

 

1.1 Function of LEDS 

 

 

 

 

 

 

 

 

 

 

2.  MAIN  FUNCTIONS                                                                                                        

 

 

2.1 HOW TO SEE THE SETPOINT 

1. Push and immediately release the 

SET

 key: the display will show the set point value. 

2.  Push  and  immediately  release  the 

SET

  key  or  wait  for  5  seconds  to  display  the       

sensor value again. 

2.2 HOW TO CHANGE THE SETPOINT

    

1. Push the 

SET

 key for more than 2 seconds to change the set point value. 

2. The value of the set point will be displayed and the 

  LED starts blinking. 

3. To change the set value push the 

  or 

  key within 10s. 

4. To set new point value, push the SET key again or wait 10s. 

2.3 HOW TO START A MANUAL DEFFROST 

Push the 

  key for more than 2 seconds and a manual defrost will start 

2.4 HOW TO LOCK THE KEYBOARD 

1. Hold the 

  and 

    keys for more than 3s. 

2. The “POF” message will be displayed and the keyboard will be locked. At this point, it will be possible only 

to see the set point or the MAX or Min temperature stored. 

3. If a key is pressed more than 3s the ”POF” message will be displayed. 

2.5 HOW TO UNLOCK THE KEYBOARD 

Hold the 

  and 

  keys together for more than 3s, till the “POF” message is displayed.   

 

3.  ALARM SIGNALS                                                                                                       

 

 

HOW  TO  SEE  THE  ALARM  AND 

RESET THE RECORDED ALARM 

1. Hold the

  or 

  key to 

display the alarm signals. 

2. When the signal is displayed, hold 

the 

SET

 key until the “rst” message 

is displayed.    Push the 

SET

 key 

again.    The “rst” message will start 

blinking and the normal temperature 

will be displayed again. 

 

 

 

 

 

 

 

On

A temperature alarm happened

MAIN FUNCTIONS
1.  How to See the Setpoint

1.  Push and immediately release the 

SET

 key: the display will show the set 

point value.

2.  Push and immediately release the 

SET

 key or wait for 5 seconds to display 

the sensor value again.

2.  How to Change the Setpoint

1. Hold 

the 

SET

 key for more than 2 seconds to change the set point value.

2.  The value of the set point will be displayed and the 

 LED starts blinking.

3.  To change the set value, push the   or   key within 10 seconds.
4.  To set new point value, push the 

SET

 key again or wait 10 seconds.

3.  How to Start a Manual Defrost

1.  Hold the 

 key for more than 2 seconds and a manual defrost will start.

4.  How to Lock the Keyboard

1.  Hold the   and   keys for more than 3 seconds.
2.  The “POF” message will be displayed and the keyboard will be locked. At 

this point, it will be possible only to see the set point or the MAX or MIN 
temperature stored.

3.  If a key is pressed for more than 3 seconds, the ”POF” message will be 

displayed.

5.  How to Unlock the Keyboard

1.  Hold the   and   keys together for more than 3 seconds, until the “POF” 

message is displayed.

ALARM SIGNALS
How to See the Alarm and Reset the Recorded Alarm

1.  Push the   or   key to display the alarm signals.
2.  When the signal is displayed, hold the 

SET

 key until the “rst” message is 

displayed. Push the 

SET

 key again. The “rst” message starts blinking and the 

normal temperature will be displayed again.

MESSAGE

CAUSE

OUTPUTS

“P1”

Room probe failure

Compressor output according 

to par. “Con” and “COF”

“P2”

Evaporator probe failure

Defrost end is timed

“HA”

Maximum temperature alarm

Outputs unchanged

“LA”

Minimum temperature alarm

Outputs unchanged

“dA”

Door open

Compressor and fans restarts

“EA”

External alarm

Output unchanged

“CA”

Serious external alarm (i1F=bAL)

All outputs OFF

“CA”

Pressure switch alarm (i1F=PAL)

All outputs OFF

Summary of Contents for KCHBC36

Page 1: ...MPS CAPACITY STORAGE CU FT HP BTU CHARGE OZ SHIP WEIGHT LBS NEMA PLUG KCHBC36 115 60 1 1 8 10 3 8 2000 2 12 161 5 15P KCHBC50 115 60 1 3 0 15 1 2 3200 2 47 310 5 15P KCHBC65 115 60 1 3 0 20 1 2 5400 3...

Page 2: ...TE CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE APPLIANCE NOTE THIS APPLIANCE CAN BE USED BY CHILDREN AGED FROM 8 YEARS AND ABOVE AND PERSONS WITH REDUCED PHYSICAL SENSORY OR...

Page 3: ...wait for 5 seconds to display the sensor value again 2 2 HOW TO CHANGE THE SETPOINT On A temperature alarm happened MAIN FUNCTIONS 1 How to See the Setpoint 1 Push and immediately release the SET key...

Page 4: ...ase call service personnel Inform them the nature of the problem the type of cooler serial number and item number provided on the nameplate at the back of the cabinet Do not open the cabinet as every...

Page 5: ...5 BOTTLE COOLER Wiring Diagram KCHBC36 KCHBC50 KCHBC65 CALL FACTORY FOR REPLACEMENT PARTS 866 339 8515 Wiring Diagram KCHBC95 CALL FACTORY FOR REPLACEMENT PARTS 866 339 8515...

Page 6: ...LER Wiring Diagram KCHBC36 KCHBC50 KCHBC65 CALL FACTORY FOR REPLACEMENT PARTS 866 339 8515 Wiring Diagram KCHBC95 CALL FACTORY FOR REPLACEMENT PARTS 866 339 8515 POWER SUPPLY POWER SUPPLY L L N N 1 1...

Page 7: ...companies use of parts other than genuine Electrolux Professional Inc parts or parts obtained from persons other than authorized service companies or external causes such as abuse misuse inadequate po...

Page 8: ...8 BOTTLE COOLER Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 9: ...U ONZAS DE CARGA PESO DE ENV O LB KG ENCHUFE NEMA KCHBC36 115 60 1 1 8 10 0 28 3 8 2000 2 12 161 73 5 15P KCHBC50 115 60 1 3 0 15 0 42 1 2 3200 2 47 310 140 6 5 15P KCHBC65 115 60 1 3 0 20 0 56 1 2 54...

Page 10: ...O DEL EQUIPO NOTA SE DEBE VIGILAR A LOS NI OS PARA IMPEDIR QUE JUEGUEN CON EL EQUIPO NOTA ESTE EQUIPO PUEDEN UTILIZARLO NI OS DE M S DE 8 A OS Y PERSONAS CON CAPACIDADES F SICAS SENSORIALES O MENTALES...

Page 11: ...he set point value Encendido Se produjo una alarma de temperatura PRINCIPALES FUNCIONES 1 C mo ver el ajuste de referencia 1 Presione y suelte de inmediato la tecla SET ajuste la pantalla muestra el a...

Page 12: ...servicio t cnico Inf rmeles de la naturaleza del problema el tipo de enfriador el n mero de serie y el n mero del equipo que figura en la placa de caracter sticas de la parte posterior del armario No...

Page 13: ...NFRIADOR DE BOTELLAS Diagrama de cableado KCHBC36 KCHBC50 KCHBC65 LLAME A LA F BRICA SI NECESITA REPUESTOS 866 339 8515 Diagrama de cableado KCHBC95 LLAME A LA F BRICA SI NECESITA REPUESTOS 866 339 85...

Page 14: ...rama de cableado KCHBC36 KCHBC50 KCHBC65 LLAME A LA F BRICA SI NECESITA REPUESTOS 866 339 8515 Diagrama de cableado KCHBC95 LLAME A LA F BRICA SI NECESITA REPUESTOS 866 339 8515 POWER SUPPLY POWER SUP...

Page 15: ...s de personas que no sean empresas de servicios autorizadas o causas externas como uso incorrecto o indebido alimentaci n el ctrica inadecuada accidentes incendios o desastres naturales 15 Los equipos...

Page 16: ...E BOTELLAS Registro de servicio N de modelo Adquirido a N de serie Ubicaci n Fecha de compra Fecha de instalaci n N de orden de compra Para llamadas al servicio t cnico Fecha Mantenimiento realizado R...

Reviews: