8 general installation of solar collectors
Kelvinator solar hot water systems
10-15mm
from horizontal
inlet
20-30mm
from horizontal
30-45mm
from horizontal
horizontal
collector rail
outlet
Note: The solar collectors (both flat panel and evacuated
tube) must be installed at an angle from the horizontal.
This is to ensure that any air in the system will travel to
the air vent valve located on the outlet connection of the
collectors.
The distance between the end of the collector rail at the
outlet side of the solar collectors and the horizontal must be:
10 - 15 mm (for one solar collector)
20 - 30 mm (for two solar collectors)
30 - 45 mm (for three solar collectors)
If the roof material is uneven where the collectors are to be
installed, then it may be necessary to add an additional 10
mm to the above distances for each collector.
Space requirements
A
B
C
C
D
Space and load bearing requirements for evacuated
tube collectors
No. of
collectors
Dimension
A (mm)
Dimension
B (mm)
Weight when
full (approx.)
1
1400
1640
47kg
2
2800
1640
94kg
3
4200
1640
141kg
Dimensions C and D
• when determining the location for the collector ensure
that there is adequate space available for the water
connections and the fixing of the mounting kit.
A
B
C
C
D
Space and load bearing requirements for flat
panel collectors
No. of
collectors
Dimension
A (mm)
Dimension
B (mm)
Weight when
full (approx.)
1
1025
2050
45kg
2
2050
2050
90kg
3
3075
2050
135kg
General installation of solar collectors