 Information servicing  19

Information servicing

Repairs to sealed components

1.   During repairs to sealed components, all electrical supplies 

shall be disconnected from the equipment being worked upon 
prior to any removal of sealed covers, etc. If it is absolutely 
necessary to have an electrical supply to equipment during 
servicing, then a permanently operating form of leak detection 
shall be located at the most critical point to warn of a 
potentially hazardous situation. 

2.   Particular attention shall be paid to the following to ensure that 

by working on electrical components, the casing is not altered 
in such a way that the level of protection is affected. This shall 
include damage to cables, excessive number of connections, 
terminals not made to original specification, damage to seals, 
incorrect fitting of glands, etc. 

• 

 Ensure that apparatus is mounted securely. 

• 

 Ensure that seals or sealing materials have not degraded 
such that they no longer serve the purpose of preventing the 
ingress of flammable atmospheres. Replacement parts shall be 
in accordance with the manufacturer's specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness 

of some types of leak detection equipment. Intrinsically safe 

components do not have to be isolated prior to working on them.

Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the 
circuit without ensuring that this will not exceed the permissible 
voltage and current permitted for the equipment in use. Intrinsically 
safe components are the only types that can be worked on while 
live in the presence of a flammable atmosphere. The test apparatus 
shall be at the correct rating. Replace components only with parts 
specified by the manufacturer. Other parts may result in the ignition 
of refrigerant in the atmosphere from a leak.

Cabling

Check that cabling will not be subject to wear, corrosion, 
excessive pressure, vibration, sharp edges or any other adverse 
environmental effects. The check shall also take into account 
the effects of aging or continual vibration from sources such as 
compressors or fans.

Leak detection methods

The following leak detection methods are deemed acceptable 
for systems containing flammable refrigerants. Electronic leak 
detectors shall be used to detect flammable refrigerants, but 
the sensitivity may not be adequate, or may need re-calibration. 
(Detection equipment shall be calibrated in a refrigerant-free 
area.) Ensure that the detector is not a potential source of ignition 
and is suitable for the refrigerant used. Leak detection equipment 
shall be set at a percentage of the LFL of the refrigerant and shall 
be calibrated to the refrigerant employed and the appropriate 
percentage of gas (25 % maximum) is confirmed. Leak detection 
fluids are suitable for use with most refrigerants but the use of 
detergents containing chlorine shall be avoided as the chlorine 
may react with the refrigerant and corrode the copper pipe-
work. If a leak is suspected, all naked flames shall be removed or 
extinguished. If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be recovered from the system, or 
isolated (by means of shut off valves) in a part of the system remote 
from the leak. Oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the brazing process.

Removal and evacuation

When breaking into the refrigerant circuit to make repairs or for any 
other purpose conventional procedures shall be used. However, 
it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to 

• 

 Remove  refrigerant;

• 

 Purge the circuit with inert gas;

• 

 Evacuate;

• 

 Purge again with inert gas;

• 

 Open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery 
cylinders. The system shall be flushed with OFN to render the 
unit safe. This process may need to be repeated several times. 
Compressed air or oxygen shall not be used for this task. Flushing 
shall be achieved by breaking the vacuum in the system with OFN 
and continuing to fill until the working pressure is achieved, then 
venting to atmosphere, and finally pulling down to a vacuum. This 
process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented 
down to atmospheric pressure to enable work to take place. This 
operation is absolutely vital if brazing operations on the pipe-work 
are to take place. Ensure that the outlet for the vacuum pump is not 
close to any ignition sources and there is ventilation available.

Summary of Contents for KSV25CRH

Page 1: ...nstallation Manual KSV25CRH KSV35CRH KSV71CRH KSV25HRH KSV35HRH KSV50HRH KSV71HRH KSV90HRH KSD25HRH KSD35HRH KSD50HRH KSD71HRH KSD90HRH KSV25HWH KSV35HWH KSV50HWH KSV71HWH KSV90HWH KSD25HWH KSD35HWH K...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu oor ar...

Page 5: ...T3 9x25 5 Remote control Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use b...

Page 6: ...d with the machine differ from appliance to appliance Dimensions are in mm unless otherwise stated 232 219 581 300 53 5 76 53 5 335 232 128 192 802 1080 297 43 43 43 65 75 65 75 Left rear side refrige...

Page 7: ...ft side drainage connection The connection of the drain pipe hose must be connected by a qua d installer in accordance with these instructions to prevent leakage 3 Attach the drain hose to the undersi...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resid...

Page 9: ...e end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to con hey are securely attached 6 Fasten the connection cable wit...

Page 10: ...and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm 885 x 554 x 365 32 5 514 340 924 x 702 x...

Page 11: ...the standard 5m then add additional refrigerant according to the below table which also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also re...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper p...

Page 13: ...hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm t...

Page 14: ...ic ring INDOOR UNIT POWER SUPPLY S 2 N L N 1 L Y G INDOOR UNIT POWER SUPPLY Please note that different models are supplied with a different combination of magnetic rings that must be installed by a li...

Page 15: ...e Pipe length and refrigerant amount Additional refrigerant required for pipe length greater than Minimum length 3m standard 5m installation can be calculated using the following equation M L 5 x A Wh...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...re are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open...

Page 18: ...sks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of v...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...Kelvinator Air Conditioning Warranty 23...

Page 24: ...ND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call int...

Reviews: