background image

20  Information servicing 

Kelvinator Air Conditioning

Information servicing

Charging procedures 

In addition to conventional charging procedures, the following 
requirements shall be followed: 

 Ensure that contamination of different refrigerants does not
occur when using charging equipment. Hoses or lines shall
be as short as possible to minimize the amount of refrigerant
contained in them.

 Cylinders shall be kept upright.

 Ensure that the refrigeration system is earthed prior to
charging the system with refrigerant.

 Label the system when charging is complete (if not already).

 Extreme care shall be taken not to overfill the refrigeration
system.

 Prior to recharging the system it shall be pressure tested
with OFN. The system shall be leak tested on completion of
charging but prior to commissioning. A follow up leak test shall
be carried out prior to leaving the site.

Decommissioning

Before carrying out this procedure, it is essential that the technician 
is completely familiar with the equipment and all its detail. It is 
recommended good practice that all refrigerants are recovered 
safely. Prior to the task being carried out, an oil and refrigerant 
sample shall be taken.

In case analysis is required prior to re-use of reclaimed refrigerant. 
It is essential that electrical power is available before the task is 
commenced. 

a)

Become familiar with the equipment and its operation.

b) Isolate system electrically.

c)

Before attempting the procedure ensure that:

 Mechanical handling equipment is available, if required,
for handling refrigerant cylinders;

 All personal protective equipment is available and being
used correctly; the recovery process is supervised at

 All times by a competent person.

 Recovery equipment and cylinders conform to the
appropriate standards.

d)  Pump down refrigerant system, if possible.

e)

 If a vacuum is not possible, make a manifold so that refrigerant
can be removed from various parts of the system.

f)

 Make sure that cylinder is situated on the scales before
recovery takes place.

g)  Start the recovery machine and operate in accordance with

manufacturer's instructions.

h)

 Do not overfill cylinders. (No more than 80 % volume liquid
charge).

i)

 Do not exceed the maximum working pressure of the cylinder,
even temporarily.

j)

 When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment
are removed from site promptly and all isolation valves on the
equipment are closed off.

k)

 Recovered refrigerant shall not be charged into another
refrigeration system unless it has been cleaned and checked.

Labelling

Equipment shall be labelled stating that it has been  
de-commissioned and emptied of refrigerant. The label shall be 
dated and signed. Ensure that there are labels on the equipment 
stating the equipment contains flammable refrigerant.

Recovery

 When removing refrigerant from a system, either for servicing
or decommissioning, it is recommended good practice that all
refrigerants are removed safely.

 When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed.
Ensure that the correct numbers of cylinders for holding the
total system charge are available. All cylinders to be used are
designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure relief valve and
associated shut-off valves in good working order.

 Empty recovery cylinders are evacuated and, if possible,
cooled before recovery occurs.

 The recovery equipment shall be in good working order with
a set of instructions concerning the equipment that is at hand
and shall be suitable for the recovery inflammable refrigerants.
In addition, a set of calibrated weighing scales shall be
available and in good working order.

 Hoses shall be complete with leak-free disconnect couplings
and in good condition. Before using the recovery machine,
check that it is in satisfactory working order, has been properly
maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.

 The recovered refrigerant shall be returned to the refrigerant
supplier in the correct recovery cylinder, and the relevant
Waste Transfer Note arranged. Do not mix refrigerants in
recovery units and especially not in cylinders. If compressors
or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that
flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning
the compressor to the suppliers. Only electric heating to the
compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.

Transportation, marking and storage for units

1.

 Transport of equipment containing flammable refrigerants
compliance with the transport regulations.

2.

 Marking of equipment using signs compliance with local
regulations.

3.

 Disposal of equipment using flammable refrigerants
Compliance with national regulations.

4.

 Storage of equipment/appliances The storage of equipment
should be in accordance with the manufacturers instructions.

5.

 Storage of packed (unsold) equipment
Storage package protection should be constructed such that
mechanical damage to the equipment inside the package
will not cause a leak of the refrigerant charge. The maximum
number of pieces of equipment permitted to be stored
together will be determined by local regulations.

Summary of Contents for KSV25CRH

Page 1: ...nstallation Manual KSV25CRH KSV35CRH KSV71CRH KSV25HRH KSV35HRH KSV50HRH KSV71HRH KSV90HRH KSD25HRH KSD35HRH KSD50HRH KSD71HRH KSD90HRH KSV25HWH KSV35HWH KSV50HWH KSV71HWH KSV90HWH KSD25HWH KSD35HWH K...

Page 2: ...air conditioner is designed for and intended to be used in normal domestic applications only Record model and serial number here Model number Serial number ENVIRONMENTAL TIPS environment Information...

Page 3: ...esponsible for their safety Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnect...

Page 4: ...room sizes are adhered to for standard installations up to 5m pipe length If larger refrigerant charges than standard are used then please consult AS NZS 60335 2 40 to determine the safe minimu oor ar...

Page 5: ...T3 9x25 5 Remote control Before screwing the remote controller holder to the wall make sure that control signals are properly received by indoor unit 2x AAA batteries In sites with poor drainage use b...

Page 6: ...d with the machine differ from appliance to appliance Dimensions are in mm unless otherwise stated 232 219 581 300 53 5 76 53 5 335 232 128 192 802 1080 297 43 43 43 65 75 65 75 Left rear side refrige...

Page 7: ...ft side drainage connection The connection of the drain pipe hose must be connected by a qua d installer in accordance with these instructions to prevent leakage 3 Attach the drain hose to the undersi...

Page 8: ...shall be installed in accordance with national wiring regulations 5 An all pole disconnection device which has at least 3mm clearances in all poles the residual current device RCD having a rated resid...

Page 9: ...e end of the connection cable fully inserting into the terminal block Tighten the terminal block screws then gently pull on the wires to con hey are securely attached 6 Fasten the connection cable wit...

Page 10: ...and nut tightly and horizontally on a concrete or rigid mount Model Outdoor unit dimensions W x H x D mm Outdoor unit weight kg Dimensions A mm Dimensions B mm 885 x 554 x 365 32 5 514 340 924 x 702 x...

Page 11: ...the standard 5m then add additional refrigerant according to the below table which also indicates the maximum pipe length and maximum height difference between indoor and outdoor units Please also re...

Page 12: ...longer than the pipe length 5 Cut pipes must follow the requirements shown in figure 12 Burr removal 1 Completely remove all burrs from the cut cross section of the pipe 2 Put the end of the copper p...

Page 13: ...hole in the wall using gum type sealer Indoor unit tubing Flare nut Pipings Fig 16 Fig 17 Outdoor unit electrical connection 1 Check that power supply to the air conditioner circuit is off 2 Confirm t...

Page 14: ...ic ring INDOOR UNIT POWER SUPPLY S 2 N L N 1 L Y G INDOOR UNIT POWER SUPPLY Please note that different models are supplied with a different combination of magnetic rings that must be installed by a li...

Page 15: ...e Pipe length and refrigerant amount Additional refrigerant required for pipe length greater than Minimum length 3m standard 5m installation can be calculated using the following equation M L 5 x A Wh...

Page 16: ...as pipe side and check that the air is entering Operation noise of the vacuum pump changes and a compound meter indicates 0 instead of minus Then retighten the flare nut 5 Keep the vacuum pump running...

Page 17: ...re are no gas leaks follow the below steps to complete an operation test Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open...

Page 18: ...sks NO SMOKING signs shall be displayed Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of v...

Page 19: ...le for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may not be adequate or may need re calibration Detection e...

Page 20: ...e dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommiss...

Page 21: ...Kelvinator Air Conditioning Notes 21 Notes...

Page 22: ...22 Notes Kelvinator Air Conditioning Notes...

Page 23: ...Kelvinator Air Conditioning Warranty 23...

Page 24: ...ND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call int...

Reviews: