THREE-PHASE CAPACITORS FOR LOW VOLTAGE POWER FACTOR 

CORRECTION 

MKP  1.88/3 - 1.88/3 H 

THE CAPACITORS COMPLY WHIT CEI EN 60831-1/2. SPECIFICATIONS  

AND MUST BE INSTALLED TAKING INTO ACCOUNT THE FOLLOWING INSTRUCTIONS 

 

Instructions 

 

Cooling 

The  capacitors  belong  to  the    temperature    rating    of  -
25°C for which the minimum standard temperature is not 
lower  than  -25°c  and  the  maximum  room  temperature  is 
not higher than +50°C. 
The  average  value  of  the  room  temperature  must  not 
exceed  40°C  over  24  hours  period  and  30°C  over  one 
year. 
If the capacitors in operation are able to modify the room 
temperature, adequate ventilation has to be provided. 
In  this  case  the  cooling  air  must  not  exceed  of  5°C  the 
maximum and medium upper limits of the category which 
the capacitors belong to. 
The  air  cooling  temperature  must  be  measured  at  the 
hottest  point,  in  stationary  conditions,  in  the  middle  of 
two units; in case of one unit only at a height equal to 2/3 
of overall unit height at a distance of 0,1m outwards. 
In  case  the  capacitors  are  frequently  exposed  to  the  sun 
radiation  or  to  any  high  surface  temperature,  units  rated 
for  voltages  and  temperatures  higher  than  nominal  ones 
must be used. 
 

Control and protection devices 

Control  and  protection  devices,  including  electrical 
connections  of  the  capacitors,  must  be  selected  to  stand 
continuous current at least equal to 1,3 times the nominal 
value  indicated  on  the  capacitors  rating  plate  (which 
would  be  obtained  with  the  sinusoidal  voltage)  with  the 
RMS  value  equal  to  the  rated  voltage  at  the  rated 
frequency. 
Taking  into  account  the  possible  conditions  of  current 
overload  and  the  higher  heating  effect  due  to  possible 
harmonic  components,  it  is  necessary  to  provide  with 
insulating  switches  or  switches  adjusted  for  currents  not 
lower  than  1,6  -  1,8  times  the  current  obtainable  with  a 
rated sinusoidal voltage with the RMS value equal to the 
rated voltage at the rated frequency. 
In  case  of  installation  of  manual  switches,  use  quick-
release switches. 
Connecting  devices  have  got  to  limit  the  current  peak  at 
the inserction according to CEI EN60831 –1 
 

Terminal tightening

 

After  some  hours  from  the  setting  at  work,  verify  the 
correct  tightening  of  the  electrical  connections  between 
the capacitors; periodically check them. 

 
 
 
 
----------------------------------------------- 
 
 

 
Attention  !

    Kemet  disclaims  all 

responsability  for  damages  of  any  kind 
caused by the utilization of its products 
non 

in 

compliance 

with 

these 

specification 

 

Discharge device

 

Each  capacitor  is  provided  with  discharge 
resistances  to  ensure  residual  voltages  lower  than 
75V within three minutes after the disconnection of 
the  same:  if  the  capacitors  are  repeatedly  charged 
and  discharged  (e.g.  automatic  equipments)  it  is 
necessary  to  adopt  additional  discharge  devices  so 
that  the  residual  must  not  exceed  10%  of  rated 
value at the moment of the charge of the capacitor. 
 

Power 

factor 

correction 

in 

presence 

of 

harmonics 

Every  time  in  the  network  there  are  AC/DC  static 
conversion  groups  for  the  feeding  or  adjustment  of 
direct  current  (DC  motors,  electrolytic  baths,  etc. 
...), static converters of frequency, induction ovens, 
the  capacitors  can  be  subject  to  current  and/or 
voltage  overloads  which  can  cause  their  quick 
wearing. 
In this case TECHNICAL SERVICE is available to 
verify  the  need  to  use  harmonic  filters  or  suitable 
capacitors for the application. 
 

Maximum current admitted

 

The  current  absorbed  by  the  capacitor  due  to  the 
presence  of  harmonics  or  to  a  voltage  higher  than 
the  rated  one  must  not  exceed  1,3  times  the  rated 
current  at  rated  frequency  and  rated  sinusoidal 
voltage. 
 

Maximum voltage admitted

 

The 

capacitors 

are 

designed 

to 

withstand 

overvoltages  without  a  particular  wearing;  the 
amplitude  of  these  overvoltages  depends  on  their 
duration,  on  the  number  of  applications  and  on  the 
temperature of the capacitors. 
Anyway  it  is  necessary  to  verify  that  the  rated 
voltage of the capacitors is not lower than the rated 
voltage of the network to which they are connected, 
taking  into  account  the  influence  of  their  presence. 
In  fact  the  life  of  a  capacitor  is  negatively 
influenced  by  an  excessive  increase  of  voltage  on 
the dielectric. 
When several capacitors are connected in parallel it 
is  necessary  to  ensure  that  the  total  current  in  the 
bus bars never exceeds 80A in nominal conditions. 
On  the  contrary,  it  is  necessary  to  reduce  the 
current  connecting  the  battery  to  the  network  with 
or more terns of cables. (See fig. 4) 
 

Grounding

 

The  capacitor  must  be  connected  to  ground  using 
the screw placed on their metal base (M8). 
 
 
 

TEMPLATE OF DRILLING

 

 

 

 

fig. 1 

 

How to connect the capacitors. 

 

 

fig. 2 

 

The capacitors should be mounted vertically in order to facilitate  

 

the cooling conditions. 

 

 

fig. 3 

 

Interconnection should be made as above including recommended 

 

applied torque. 

 

 

  fig. 4 

 

  Parallel connection of capacitors. 

 

Warranty

 

 

Our  Company  guarantees  the  capacitors  Three  Phase  C88H  Series  for  a 
period of 24 (Twenty four) months from date of purchase as evidenced by 
a our invoice number

 