Installation Instructions Kemlan Power Flue Horizon Gas Fireplaces

Before Installation

The Horizon powered flue system shall be installed by
authorized personnel in accordance with the
manufacturer’s installation instructions, local gas fitting
regulations, municipal building codes, electrical wiring
regulations, and any other statutory regulations. Contact
your local building authorities about restrictions and
installation inspections that may be required. If in doubt
contact your local dealer or Kemlan’s Head office.

IMPORTANT AUSTRALIAN CODES:

Australian Standards AS 5601 Gas Installation

Australian Standards AS 3000 Electrical 

Important Safety Notes

Comply with all instructions in manual including 
clearances to combustible material.

Do not operate without fully assembling all 
components.

All open gas fires require ventilation in the room. 

Do not connect to any other air distribution duct or 
system.

When using an internal fan system an A.G.A 
approved cowl is required at flue terminal.

Air movement of systems- A decorative gas log fire 
must not be installed where the operation of any 
ventilation system, fan or air blower could in any 
circumstances cause the air pressure to be less than 
atmospheric at the appliance.

Do not block or restrict chimney. The power flue 
system operates on pressure switches opening a 
valve for gas to flow. If flue is blocked the system will 
cut out.

After installing appliance check that the flue draws
well with smoke pellet.

Kemlan recommends that all gas fires be serviced 
every year.

All gas units must be fitted by a licensed gas fitter.

It is the responsibility of the gas fitter to follow the 
regulations set out in the Gas Code that dictate the 
procedures to follow when installing a gas appliance, 
particularly regarding gas pipe sizing and checking of 
pressures. (see page 10)

Installation

1

Access must always be available to the fan system for 
servicing. If installing the internal fan system an 
access panel of 400mm x 400mm needs to be 
installed with a clearance of 100mm over the top of 
fan to lift out. 

2

The power flue Horizon system is supplied with all 
required electrical fittings. Work needs to be 
undertaken by a licensed electrician if extending 
wiring. Wiring requires clearance of minimum 
100mm to flues and fireplace body due to heat. See 
Wiring diagram page. Wiring must be positively
secured away from heat source.

3

An isolation switch needs to be provided if 
connecting within fireplace framework.

4

Build frame to specifications provided.

5

Unit located on 10mm fiber cement sheeting. 
Sheeting requires 5 x 50mm holes drilled for air 
access to gas burner.

6

Unit, flues, fan and muffler to be installed prior to 
plastering. Muffler is installed prior to fan to 
eliminate fan noise. The muffler is attached to spigot 
by a 150mm reducer.

7

Gas line run to desired position prior to plastering.

8

A minimum height of 150mm from floor needs to be 
available for use of front fascia on firebox.

9

Clearance of 75mm above horizontally run flue. 
50mm to vertical flue.

10 Maximum horizontal run of 5m.

11 All flue components to be riveted together.

12 Ventilation is required under fireplace to allow for 

sufficient air to gas burner. (Note Elevation drawing)

13 Rooms with Gas Open Fires require fresh air vents 

of 400sq centimetres for each Decorative Gas, Coal 
Fire.

Summary of Contents for 1100 Cantilever

Page 1: ......

Page 2: ...l Type 2 Power Flue Decorative Gas Fireplace DATA PLATE Refer to data plate for information in respect to gas pressure consumption and gas type Natural or LPG Data Plate is located under the gas burner and is accessed by lifting front access panel or removing base plate Location Requirements Power flue systems utilise a fan assisted draft to ensure products of combustion are exited through a flue ...

Page 3: ...to 50 MJ h input 300 Appliances over 50 MJ h input 500 b From the ground or above a balcony 300 c From a return wall or external corner 500 d From a gas meter M 1000 e From an electricity meter or fuse box P 500 f From a drain or soil pipe 150 g Horizontally from any building structure unless appliance approved for closer installation or obstruction facing a terminal 500 h From any other flue term...

Page 4: ...d by a licensed gas fitter It is the responsibility of the gas fitter to follow the regulations set out in the Gas Code that dictate the procedures to follow when installing a gas appliance particularly regarding gas pipe sizing and checking of pressures see page 10 Installation 1 Access must always be available to the fan system for servicing If installing the internal fan system an access panel ...

Page 5: ...ons Kemlan Power Flue Horizon Gas Fireplaces Measurement and Specifications of Fan Power Flue INTERNAL FAN SINGLE SIDED REAR EXIT INTERNAL FAN EXTERNAL FAN DOUBLE SIDED SIDE EXIT CANTILEVER REAR EXIT H 1210 1210 1210 H H 1010 1010 1010 H ...

Page 6: ...n Instructions Kemlan Power Flue Horizon Gas Fireplaces Framing Dimensions DOUBLE SIDED SINGLE SIDED OUTSIDE WALL OUTER FLUE ACTIVE FLUE REDUCER FAN MOTOR FAN HOUSING FLASHING COVER CEILING ROOFING MATERIAL FLASHING COVER FAN HOUSING SCALE 1 20 SCALE 1 20 SCALE 1 7 MAX HEIGHT BASED ON 2 4M CEILING ...

Page 7: ...uctions Kemlan Power Flue Horizon Gas Fireplaces Section of Fan Power Flue INTERNAL FAN SIDE EXIT EXTERNAL FAN SIDE EXIT SINGLE SIDED ELEVATION MAX HEIGHT 22OMM BASED ON 2 4M CEILING CANTILEVER ELEVATION MAX HEIGHT 300MM BASED ON 2 4M CEILING Elevation of Fan Power Flue ...

Page 8: ... burner will then ignite from pilot Burner is turned off by turning off wall switch Power flue system does not have a high low switch burner switch Laying the fire Coal Pebble Evenly spread a bag of Vermiculite into the burner tray Tray should be completely filled to the top with Vermiculite to a depth of approximately 45mm Unpack the coals pebbles contained in a clear plastic bag and lay a row of...

Page 9: ...es Laying the fire Coal Pebble MARK 2 COALS 440 500 390 X 240 MARK 2 COALS 600 460 X 260 MARK 2 COALS 700 580 X 260 MARK 2 PEBBLES 700 580 X 260 MARK 2 COALS 700 800 600 X 155 MARK 2 PEBBLES 700 800 600 X 155 MARK 2 COALS 1000 992 X 155 MARK 2 PEBBLES 1000 922 X 135 ...

Page 10: ...les on the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log NO S 2 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire L O G S P O S I T I O N I N G O F A L L L O G S It is important to follow the log recommended positioning Log NO 6 10 9 and...

Page 11: ...laced on the rear log in the centre of the burner Charred effect facing toward the left of the burner The front rests on logs 2 3 on the join LOCATE LOG NO 10 This log is located on the rear log in the position where the log reduces in height The charred end is located on the front log 3 with the charred effect facing toward the right hand side 4 LOCATE LOG NO 4 Place it on the left side of the re...

Page 12: ...front log no s 2 and 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire L O G S P O S I T I O N I N G O F A L L L O G S It is important to follow the log recommended positioning Not doing so can adversely effect the operation of the appliance This diagram sho...

Page 13: ...to the large rear log no 1 6 LOCATE LOG NO 7 The charred effect of the log is positioned on the smaller coal in the centre of the burner on the right hand side The right hand side of the log is positioned between the front metal upright on the side 4 LOCATE LOG NO 4 This log is placed with the thinner edge on the smaller coal The charred effect is facing towards the front of the burner The whole l...

Page 14: ...n Horizon electronic power flue ignition system Working correctly there will be no spillage Unit should cut out if not enough draw to ensure proper functioning 2 Initially the Kemlan coal fire may burn with a slightly blue flame After approximately 20 minutes the fire will settle down and burn with a yellow flame 3 As with all gas fires your gas coal pebble or log fire should be regularly serviced...

Page 15: ...Notes For further information contact Kemlan Australia Head Office 59 Pineapple St Zillmere QLD 4034 Telephone 07 3263 8488 Facsimile 07 3263 6452 www kemlan com ...

Reviews: