25/02/2021
Ver. 1
20
DIRECT IGNITION
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
PILOT WILL NOT LIGHT
1) NO GAS
- CHECK FOR GAS SUPPLY AND
TURN ON ALL CONNECTIONS
- CHECK GAS PRESSURE
- CHECK PILOT AND CLEAN INJECTOR
2) NO SPARK AT PILOT
- CHECK ELECTRIC SUPPLY AND
TURN ON ALL SWITCHES
- CHECK ALL CONNECTIONS
- CHECK SPARK ELECTRODE CONNECTIONS
AND REPLACE ELECTRODE IF DAMAGED.
- CHECK SOLENOID CONNECTIONS AT VALVE
PILOT LIGHTS BUT
1) FLAME SENSOR NOT
- CHECK ELECTRODE IS IN PILOT
VALVE DOES NOT OPEN TO LIGHT MAIN
BURNER
SENDING SIGNAL TO OPEN
VALVE
FLAME
- CHECK ELECTRODE CONNETCTIONS
- CLEAN ELECTRODE
- CHECK ELECTRODE FOR DAMAGE
- REPLACE ELECRODE
2) MODULE NOT SENDING
- REPLACE MODULE
SIGNAL TO OPEN VALVE
3) FAULTY VALVE
- REPLACE VALVE
FLAME FAIL LOCKOUT
1) POWER FAILURE
- TURN ON/OFF SWITCH OFF AND
UNIT HAS DETECTED LOSS OF FLAME
AND LOCKED OUT
ON AGAIN TO RESET ONCE POWER
ESTABLISHED
2) GAS SUPPLY
- CHECK GAS PRESSURE AND ADJUST
- RESET AT ON/OFF SWITCH
3) DIRTY ELECTRODE
- CLEAN ELECTODE OR REPLACE
4) PILOT BLOCKED
- CLEAN PILOT INJECTOR
5) PRESSURE SWITCHES
NOTE: TECHRITE IGNITION PACK FLASH CODES
(RED LED) TO IDENTIFY PROBLEM.
Installation Instructions Kemlan Three Sided Natural Draft
Electronic Ignition Gas Fireplaces