Manual KHS Mini System Control MASTER
13
Connection of KHS-CONTROL-PLUS cable-plug connector
Ill. 6.12:
Schematic diagram of the preparation of the sensor top to make cable-
plug connection of the KHS-CONTROL-PLUS
6.2.2.7
Connection of KHS Temperature sensor Pt 1000 (Figure 628 0G)
RD = red = 18
RD = red = 19
W = white = 20
W = white = 21
Ill. 6.13:
Schematic diagram of connection of KHS Temperature Measurement
Valve Pt 1000
6.2.2.8
Connection of KHS drain with overflow monitor (Figure 688 00)
Note:
In the as delivered state, a bridge
strand is plugged between Terminals
22 and 23. It must be removed before
connecting the KHS drain.
W = white = 22
BN = brown = 23
Ill. 6.14:
Schematic diagram of connection of the KHS drain with overflow monitor
1. Cut off top of cap 2. Route cable through
3. Screw cable to sensor
4. Put on the
cap